B. Clearances
WARNING! Risk of Fire!
You must comply with all minimum air space clearances to combustibles as specified in Figure 3.2.
DO NOT
pack required
air spaces with insulation or other materials. Framing or finishing material used on the front of, or in front of, the fireplace
closer than the minimums listed must be constucted entirely of non-combustible materials (i.e., steel studs, concrete board,
etc.). Failure to comply may cause fire.
Figure 3.2 Clearances to Combustible Materials
(ceiling)
(roof)
(ceiling)
2 in. (51 mm) min.
Attic
Insulation
Shield
Ceiling Firestop
(attic)
Storm Collar
Roof Flashing
2 in. min.
(51 mm)
2 in. (51 mm) min.
2 in. (51 mm) min.
Ceiling Firestop
Offset/Return with
hanger straps
2 in.
(51 mm)
min.
2 in. (51 mm) min.
Must have 2 in. (51 mm)
minimum clearance
to header
Electrical wires must be 3-1/2: (89mm)
from top
0 in. to level
of standoffs
1 in. (25mm) to side of appliance
1/2 in. (13 mm) to back
of appliance
0 in.
to floor
36 in. (914 mm)
standoffs to ceiling
Chimney Air Kit required with SL chimney
11
Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14