10.Remove and clean the Y strainer. Ensure a catch-pan or bucket is placed under the strainer
in order to catch liquid when strainer is removed.
11. Reinstall Y strainer and open valve (if installed by user).
12. Fill the reservoir back to the “max” line and set GHT switch to desired state (ON/OFF).
Figure 21-3 Coolant Setpoints in Lynx
Table 21-2 GHT VFD Speed Settings
Heat Trace
Length [ft]
Tube Volume (based
on 1/2” tubing)
Flow Rate
[gpm]
VFD Speedpot
Settings
250
1.85
0.98
48
500
3.75
1.45
68
750
5.6
1.91
88
1000
7.5
2.39
100
1250
9.4
2.86
100
1500
11.25
3.33
100