F
AULT
M
ESSAGES
, P
OWER
G
EN
121
2024
‘Duct Jacket’ temperature
critical
Temperature on the cooled
exhaust duct is above
230°F/110°C
• If sensor readings are
unstable, verify sensor
seated well. Replace
sensor.
• Check for flow reading
and pump feedback.
2025
Burner blower not spinning
Blower not getting power,
signal harness unplugged.
blower seized or damaged,
• Verify disconnect switch
in '1' position
• Inspect all fuses on FPC.
• If pump feedback is zero,
check QEC output C
configuration.
• Inspect harnesses and
connectors are firmly
seated. Replace if
necessary.
• Replace blower.
• Replace FPC.
Table 15-3 PowerGen Error Messages, User Clearable
Fault Code
Description
Possible Causes
Содержание PowerGen 5650 Series
Страница 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Страница 8: ...iv...
Страница 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Страница 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Страница 49: ...QNERGY LYNX SOFTWARE 37 Figure 6 17 FPC Configuration Tab Figure 6 18 FPC Config System Settings...
Страница 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Страница 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Страница 194: ...POWERGEN OPTIONAL FEATURE SETS 182...