C
OMMISSIONING
P
ROCEDURE
91
Figure 12-20 Blower Tuning Screws
2.Attach a Lambda sensor to the exhaust outlet, at the threaded boss. Turn on the gauge
and make sure it is calibrated, reading should be 20.9.
3. In Lynx FPC/Config Tab, Set “HHT Setpoint” too 600 °C and click set.
Figure 12-21 Head Temp Setpoint