127
4018
Cabinet door open
Cabinet door is open, sensor
cable is unplugged, magnet
spacing incorrect, sensor
failed.
• Close cabinet door
• Check black wire
connected to FPC board
at P11 (bottom right
corner).
• Adjust location of sensor
located in cabinet by
bending the bracket
slightly outwards towards
the door.
4019
Engine Bay Top/Bottom
temperature difference is too
high
False warning on FW 1.5.1,
NTC’s plugged into wrong
ports, exhaust leak into
engine bay, bad sensor.
4020
Cold Protection
Applicable for LTS units only.
Gas valve temperature below
-15°C. see LTS cold start
procedure. Gas valve heater
will turn off at 20°C.
4021
GHT return temp sensor failed
Sensor failed, open or short
circuit, bad wiring.
• Inspect the channel NTC7
on the FPC is seated well.
• Inspect connector and
cable for damage.
• Replace sensor.
4022
GHT supply temp sensor failed
Sensor failed, open or short
circuit, bad wiring.
• Inspect the channel NTC8
on the FPC is seated well.
• Inspect connector and
cable for damage.
• Replace sensor.
Table 15-5 PowerGen Error Messages, Warning
Fault Code
Description
Possible Causes
Содержание PowerGen 5650 Series
Страница 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Страница 8: ...iv...
Страница 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Страница 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Страница 49: ...QNERGY LYNX SOFTWARE 37 Figure 6 17 FPC Configuration Tab Figure 6 18 FPC Config System Settings...
Страница 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Страница 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Страница 194: ...POWERGEN OPTIONAL FEATURE SETS 182...