F
AULT
M
ESSAGES
, P
OWER
G
EN
116
1012
Internal circulating pump
electrical fault
Pump supply voltage is out of range
(Feedback 85%) or short on feedback
signal (Feedback 100%), bad pump
electronics.
1014
QEC did not wake up
System wiring problem faulty QEC/FPC
hardware.
Power cycle QEC.
1015
Gas over-pressure
Gas pressure downstream of the
PowerGen internal regulator is above
70mBar for 2 seconds.
Gas liquids in fuel line, regulator removed,
regulator malfunction, regulator exposed
to extreme low temperatures while
supply pressure is turned on.
• Reduce gas regulator over pressure
setting.
• Verify no fuel liquids in fuel train by
removing the yellow flexible fuel line.
• Install necessary gas drying
equipment.
• Replace internal regulator.
Table 15-2 PowerGen Error Messages, Service Required
Fault Code
Description
Possible Causes
Содержание PowerGen 5650 Series
Страница 1: ...7045 102089 000 June 1 2021 Installation Operation Manual FOR A QUALIFIED INSTALLER...
Страница 8: ...iv...
Страница 12: ...iv Figure 21 9 ATS Enclosure 179 Figure 21 10 Battery Connection Schematic 181...
Страница 28: ...SYSTEM INTRODUCTION 16 Figure 3 6 P ID Diagram...
Страница 49: ...QNERGY LYNX SOFTWARE 37 Figure 6 17 FPC Configuration Tab Figure 6 18 FPC Config System Settings...
Страница 69: ...QNERGY LYNX SOFTWARE 57 Figure 6 57 FPC FEB QEC Firmware Update...
Страница 158: ...MAINTENANCE 146 Figure 17 2 Radiator and Over Flow Tank...
Страница 194: ...POWERGEN OPTIONAL FEATURE SETS 182...