Installation
Planning the Installation
D000140-001 B
1-3
A
Cable Handling and Bend Radius
Provide proper strain relief by adhering to the following guidelines:
For copper cable, the temporary 90-degree bend can never be more than 0.5
inches tighter than the values listed above for any assembly. This is the absolute
minimum sustained bend radius for each cable AWG size. This measurement is
the distance from the switch panel to the point where the cable makes a
90-degree bend. In other words, this number includes the distance from the
connector stand-off from the panel surface.
Figure 1-1 Copper Cable Bend Radius
Table 1-1. IB Copper Cable Guidelines
IB Copper Cable Bend Radii
American Wire Gauge (AWG)
Size Cable
Bend Radius
26
2.43 inches
28
2.28 inches
30
1.98 inches
Содержание QLogic 12000 Series
Страница 1: ...D000140 001 B QLogic 12000 Hardware Installation Guide...
Страница 42: ...Installation 12800 360 Installation 1 34 D000140 001 B S Figure 1 27 12800 360 Front and Rear Cabling...
Страница 53: ...Installation 12800 360 Installation D000140 001 B 1 45 A Figure 1 37 Fasten the Chassis to the Back of the Rack...
Страница 92: ...QLogic 12000 Series Product Specifications 12800 Series A 8 D000140 001 B S Notes...
Страница 97: ...Safety and Regulatory Compliance Information Safety Information D000140 001 B 5 A 2...
Страница 108: ...Safety and Regulatory Compliance Information Safety Information B 16 D000140 001 S 7 QLogic 12000 MPFD EMI...
Страница 109: ...Safety and Regulatory Compliance Information Safety Information D000140 001 B 17 A...
Страница 110: ...Safety and Regulatory Compliance Information Safety Information B 18 D000140 001 S Notes...
Страница 113: ...Serial Port Pinouts D000140 001 B C 3 A...
Страница 114: ...Serial Port Pinouts C 4 D000140 001 B S Notes...
Страница 125: ......