77
Appendix D - Limits and Fault Codes
Condition
Factory setting
(VAC) or (Hz)
Range (VAC)
Maximum
Trip Time (s)
Voltage phase high
304.8
304.8 – 332.5
1.0
Voltage phase low
243.9
216.1 – 243.9
2.0
Voltage phase fast high
332.5
332.5 – 360.2
0.16
Voltage phase fast low
138.6
138.6
0.16
Line frequency low
59.3 Hz
59.3
0.16
Table D-1 Voltage and Frequency Limits
Condition
Adjustable Setting (VAC) or (Hz)
AC Voltage Field Adjustable Trip Points
(% of Normal)
-22% to +20%
Accessible Range of Low Frequency Setting (Hz)
(Limits of Accuracy Frequency Measurement +/-0.1 Hz)
Adjustable low trip 57.5-59.8
High trip fixed at 60.5
Accessible range of Trip Times
(Limits of Accuracy Time Measu/- 0.1 sec.)
.16 to 300 seconds
Table D-2 Adjustable Voltage and Frequency Limits
260kW Faults and Warnings
Fault Variables
The 260kW firmware will utilize one, 16-bit variable (fault) to indicate a fault condition.
Each bit in this fault variable represents the fault type or category. The bit assignments
and specific fault variables for the fault categories are as follows:
Description
Bit
Nbr.
Hex
Value
Decimal
Value
Modbus register number = 42102
Drive fault
0
1
1
Voltage fault
1
2
2
Grid fault
2
4
4
Temperature fault
3
8
8
System fault
4
10
16
Latching fault
15
8000
32768
Table D-3 Main Fault Categories
APPENDIX D
Содержание PVP260kW
Страница 1: ...97 600100 24 B02 PVP260kW Inverter INSTALLATION OPERATION MANUAL ...
Страница 2: ......
Страница 4: ...ii ...
Страница 6: ...iv ...
Страница 8: ...vi ...
Страница 48: ...36 ...
Страница 62: ...50 ...
Страница 86: ...74 ...
Страница 87: ...75 Appendix C Mechanical Drawings Figure C 1 Mechanical Drawings APPENDIX C ...
Страница 88: ...76 Figure C 2 Mechanical Drawings ...
Страница 94: ...82 ...
Страница 96: ...84 ...
Страница 104: ...92 Notes ...
Страница 105: ......
Страница 106: ...PO Box 7348 Bend OR 97708 P 541 312 3832 www pvpowered com ...