59
7. Maintenance & Troubleshooting
!
DANGER
AC and DC voltages will still be present at the inverter AC and DC landing points
unless utility connection circuit breaker and PV array inputs are disconnected.
!
DANGER
Before attempting any maintenance or troubleshooting, turn OFF AC and DC
power to the inverter.
7.1 Visual Inspection
PV Powered recommends visually inspecting the inverter every time it is serviced. Start
by observing the front, back and sides of the inverter for damage, foreign objects, or dust
and debris that may have accumulated around the inverter. Remove dirt and debris from
the area around the inverter at least every six months.
7.2 Annual Preventative Maintenance
Maintenance Checklist
The following maintenance should be performed annually by a qualified service person.
See
Appendix E - Annual Maintenance Requirements Checklist
for a checklist of these
required maintenance items.
A. General Inspection & Cleaning
1.. Record.general.site.conditions.
2.. Record.inverter.performance.data.from.inverter.display.
3.. Record.environmental.conditions.
4.. Remove.dirt.and.debris.from.underneath.the.inverter.
5.. Inspect.and.clean.interior.of.inverter.
6.. Inspect.air.filter.and.clean.or.replace.
7.. Confirm.presence.of.required.site-specific.safety.equipment.
8.. Confirm.presence.of.product.documentation.
B. Connections and Wiring
9.. Complete.visual.inspection.of.electrical.connections.and.wiring.
10.. Complete.mechanical.inspection.of.connections.and.wiring.
11.. Measure.torque.of.all.electrical.connections.and.re-torque.as.needed.
12.. Complete.thermal.scan.of.inverter.connections,.wiring.and.electronics.
M
A
IN
TE
N
A
N
C
E &
TR
O
U
B
LE
SH
O
O
TIN
G
Содержание PVP260kW
Страница 1: ...97 600100 24 B02 PVP260kW Inverter INSTALLATION OPERATION MANUAL ...
Страница 2: ......
Страница 4: ...ii ...
Страница 6: ...iv ...
Страница 8: ...vi ...
Страница 48: ...36 ...
Страница 62: ...50 ...
Страница 86: ...74 ...
Страница 87: ...75 Appendix C Mechanical Drawings Figure C 1 Mechanical Drawings APPENDIX C ...
Страница 88: ...76 Figure C 2 Mechanical Drawings ...
Страница 94: ...82 ...
Страница 96: ...84 ...
Страница 104: ...92 Notes ...
Страница 105: ......
Страница 106: ...PO Box 7348 Bend OR 97708 P 541 312 3832 www pvpowered com ...