Grid-Tied Residential Inverters
Installation and Operation Manual
17
4. OPERA
TIONS
4. Operations
WARNING
Before turning on the inverter, ensure that the front panel is closed properly.
!
WARNING
The heat sink can reach temperatures in excess of 158ºF (70ºC). Do not touch the heat
sink when in use, and do not place anything on top of the heat sink.
!
To start up the inverter, complete the following steps in the order indicated:
Turn the
1.
AC breaker ON
.
Verify that the RED LED light is illuminated.
2.
Verify the PV is wired in accordance with the grounded scheme (either positive or
3.
negative). Confirm that the PV array open circuit voltage is at or below the level
specified in Table 3-4.
Turn the
4.
DC disconnect ON
.
NOTE:
PV Powered recommends that a padlock be attached to prevent
unauthorized access or damage to the inverter.
After five minutes, the inverter will start to produce power if all necessary operating
5.
conditions are met.
4.1 Start up Procedures
Содержание 1100