Grid-Tied Residential Inverters
Installation and Operation Manual
9
Figure 3-5 Communications, AC and DC Ports
WARNING
Electrical connections must be completed in accordance with local electrical codes
and the National Electrical Code (NEC), ANSI/NFPA 70. Use 10 AWG, minimum
90
o
C (194
o
F), copper wire for all inverter electrical connections. Voltage drop as well
as other considerations may dictate using larger wire sizes.
!
WARNING
Make sure the main breaker in the main utility breaker box is switched OFF before
wiring the inverter. This breaker should be switched ON only after all wiring has been
completed as described in this manual.
!
WARNING
Follow the order listed below to wire the inverter. Failure to do so may result in
hazardous voltages or disconnection of contacts.
!
CAUTION
The input and output circuits are isolated from the enclosure. System grounding,
when required by Sections 690-41, 690-42, and 690-43 of the National Electric Code
(NEC), ANSI/NFPA 70-1999, is the responsibility of the installer.
!
NOTE:
PV Powered recommends sizing wire of one percent voltage drop for
AC and one percent voltage drop for DC.
IMPORTANT:
When mounting the inverter outside, use rain-tight or wet-location conduit
hubs that comply with the requirements in the Standard for Fittings for Conduit and Outlet
Boxes, UL 514B.
Terminal connections for the inverter are located inside the inverter on the circuit board at
the bottom of the cabinet. The AC and DC terminals accept wires up to 6 AWG.
Do not proceed with the electrical connection of the inverter until it has been properly
mounted.