8
Inverter Model
Circuit
Breaker Required
PVP1100
1 pole 15A
PVP2000
2 pole 15A
PVP2500
2 pole 20A
PVP2800
2 pole 20A
PVP3000
2 pole 20A
PVP3500
2 pole 20A
PVP4600
2 pole 30A
PVP4800
2 pole 30A
PVP5200
2 pole 30A
Table 3-1 Required Branch Circuit Protection
Inverter Voltage and Frequency Limits
The inverter is factory-calibrated to the voltage and frequency limits specified in Table
3-2. This adjustable range can be set by PV Powered field technicians.
Condition
Factory
Setting
Adjustable Range
(VAC) Models 2500,
3500, 4600, 4800, 5200
Adjustable Range
(VAC) Models 1100,
2000, 2800, 3000
Maximum
Trip Time(s)
Voltage phase high
132.0
132.0 - 138.0
132.0 - 142.0
< 1 second
Voltage phase low
105.6
99.6 - 105.6
95.6 - 105.6
< 2 seconds
Voltage phase fast high
144.0
144.0 - 150.0
144.0 - 156.0
< 160ms
Voltage phase fast low
60.0
54.0 - 60.0
< 60.0
< 160ms
Voltage high line to line
(240V inverters)
264.0
Voltage low line to line
(240V inverters)
211.0
Voltage high line to line
(208V inverters)
228.8
Voltage low line to line
(208V inverters)
183.0
Line frequency low
59.3 Hz
n/a
< 160ms
Line frequency high
60.5 Hz
n/a
< 160ms
Table 3-2 Inverter Voltage Frequency Limits