Table A-1 PVP1100 through PVP2800 Specifications
Specifications
PVP1100
EVR
PVP1100
PVP2000
EVR
PVP2000 PVP2500 PVP2800
Maximum DC Input Voltage (VOC)
500VDC
DC Voltage Operating Range (V)
115VDC-
450VDC
150VDC-
450VDC
115VDC-
450VDC
150VDC-
450VDC
140VDC-
450VDC
180VDC-
450VDC
DC MPPT Range (V)
115VDC-
380VDC
150VDC-
380VDC
115VDC-
380VDC
150VDC-
380VDC
140VDC-
380VDC
180VDC-
380VDC
DC Imp Maximum Current (A)
10A
8A
18A
14A
20A
16A
DC Isc Maximum Current (A)
26A
AC Operating Range (V)
105.6V-
132.5V
211V-
264V
211V-
264V
183V-
229V
AC Frequency Range (Hz)
59.3Hz-60.5Hz
AC Nominal Voltage (V)
120V
240V
240V
208V
Normal Output Frequency
60Hz
Synchronization in Rush Current
< 2.0A
8.4A
< 2.0A
Power Factor
0.99 - 1.0 at >50% Power
0.95 - 1.0
0.99 - 1.0 at
>50% Power
AC Maximum Continuous Current (A)
9.5A
9A
12A
14A
Recommended Breaker Size
15
20
Output Overcurrent Protection
20A
26A
20A
Continuous Output Power (Watts)
1100
2000
2500
2800
Maximum Continuous Output Power
(Watts)
1100
2000
2500
2800
Enclosure
Steel- NEMA 3R to UL 50 Standards
Dimensions (W x D x H)
16” x 7.5” x 21.75”
Weight (lbs.)
55lbs
65lbs
70lbs
Cooling
Natural Convection - Heat Sink
Relative Humidity
0% to 100% Condensing
Ambient Temperature Range
-25
o
C to + 40
o
C
Environmental Rating
NEMA 3R
Listings
UL 1741, IEEE 1547, IEEE 519, IEEE 929, IEEE 620