The
third parameter
for each relay determines the
assignment
or
condition
of the relay, where required.
P212, 222, 232, 242, 252
–
Relay Alarm ID/Pump Group
P211, 221, 231, 241, 251 = 2 (Step Time)
If the relay is selected for Step Time, then this parameter is used to assign
the relay to the 0 =
Open
condition (increase level) or 1 =
Close
condition
(decrease level).
The
fourth parameter
,
fifth parameter
and
sixth parameter
are set to
determine the
switch points, “
ON
” and “
OFF
” for the relay and where
required the order of start. See
control function
, table (
P211, 221, 231,
241, 251
) for further information.
P213, 223, 233, 243, 253
–
Relay Setpoint 1
P211, 221, 231, 241, 251 = 1 (Time)
This
parameter determines the “Time Period” that the relay will remain “ON”.
Relay Setpoints are entered in Minutes. See the appropriate relay function
tables (P211, 221, 231, 241, 251) for further information.
P211, 2210, 231, 241, 251 = 2 (Step Time)
Relay Setpoint 1 is entered in values of Measurement Units (P104)
See the appropriate relay function tables (P211, 221, 231, 241, 251) for
further information.
P214, 224, 234, 244, 254
–
Relay Setpoint 2
P211, 221, 231, 241, 251 = 1 (Time)
This parameter
determines the “Cycle Time” for the opera
tion of the relay.
See the appropriate relay function tables (P211, 221, 231, 241, 251) for
further information.
P211, 2210, 231, 241, 251 = 2 (Step Time)
Relay Setpoints are entered in Seconds to set Drive Period, the time that the
relay will remain
‘
ON
’.
See the appropriate relay Function tables (P211, 221, 231, 241, 251) for
further information.