Bargraph
P829 Bargraph
By default, the Bargraph will be representative of the reading obtained, as
determined by the
Mode P100
.
The options, dependant on the
value
entered for
Mode P100
, are as
follows:
OPTION
DESCRIPTION
1 = Level
Bargraph will be representative of
Level
2 = Head (Default)
Bargraph will be representative of
Head
3 = Flow
Bargraph will be representative of
Flow
mA Output Parameters
Range
P830 mA Range
This parameter determines the range of the mA output, from the following:
OPTION
DESCRIPTION
0 = Off
mA output disabled
1 = 0 to 20 mA
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 0 mA. If
the reading is 100% the output is 20 mA.
2 = 4to 20 mA
(Default)
mA output directly proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 4 mA. If
the reading is 100% the output is 20 mA.
3 = 20 to 0 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA.
If the reading is 100% the output is 0 mA.
4 = 20 to 4 mA
mA output inversely proportional to the
mA mode
(
P831
), so if the reading is 0% the output is 20 mA.
If the reading is 100% the output is 4 mA.