CHAPTER 6 PARAMETER LISTING AND DESCRIPTION
Application Parameters
Operation
P100 Mode of Operation
This parameter sets the mode of operation, when in run mode, and can be
set to one of the following:
OPTION
DESCRIPTION
1 = Distance (Default)
Display shows the distance from the transducer face
to the surface of the material measured.
2 = Level
Shows how full a vessel is.
3 = Space
Shows how empty a vessel is.
4 = OCM Head
Display shows how high the head is.
5 = OCM Flow
Display shows the instantaneous flow.
P
101 Xducer (Transducer)
This parameter should be set to the transducer being used with the unit, and
can be set to one of the following:
OPTION
DESCRIPTION
1 = dB3 (Default)
Transducer is a dB3. Range = 4.92 to 118.11 inches
2 = dB6
Transducer is a dB6. Range = 11.81 to 236.22 inches
3 = dB10
Transducer is a dB10. Range = 11.81 to 393.70 inches
4 = dB15
Transducer is a dB15. Range = 19.68 to 590.55 inches
7 = dBS6
Transducer is a dBS6. Range = 7.87 to 236.22 inches
8 = dBMach3
Transducer is a dBMach3. Range 0 to 95.58 inches
*11 = dBR16
Transducer is a mmWAVE radar. Range = 3.03 to 629.9 inches
*12 = dBR8
Transducer is a mmWAVE radar. Range = 3.03 to 315 inches
Important Notice
*Please consult your local Pulsar distributor for the versions of firmware
that the mmWAVE radars are available in.