FLOWCERT LITE (UL) INSTRUCTION MANUAL
116
Operation
P831 mA Mode
This parameter determines how the mA Output relates to what is measured.
By
default,
it operates exactly the same as the display (
P100
), but it can be
set to operate as follows:
OPTION
DESCRIPTION
0 = Default
mA output relative to
Mode
P100
1 = Distance
mA output relative to
Distance
.
2 = Level
mA output relative to
Level
.
3 = Space
mA output is relative to
space
.
4 = OCM Head
mA output relative to
OCM Head
5 = OCM Flow
mA output is relative to
OCM
flow
.
6 = Average Flow
mA output is relative to
Average flow
Setpoint
By
default,
the mA Output will represent the
empty
(
0
or
4mA
dependant
on
(
P830
)
mA Range
) and
100%
of the operational
span
(
20mA
), but you
may wish to have the output represent a section of the operational span. For
example, the application has an operational span of 6 metres, but
output
is
to
represent
empty
(
0
or
4mA
dependant on
(
P830
)
mA Range
) to a
level
of
5 metres
(
20mA)
. If so P834 (Low Level) should be set to 0.00 metres and
P835 (High Level) should be set to 5 metres.
P834 mA Low Level
This parameter sets the level, distance, or space, depending on the selected
mA Out Mode
(
P831
) at which the low mA output will occur
(
0
or
4mA
dependant on
(
P830
)
mA Range
).
Default = 0.000 inches
P835 mA High Level
This parameter sets the level, distance or space, depending on the selected
mA Out Mode
(
P831
) at which the high mA output will occur
(
20mA
).
Default = 228.346 inches