FLOWCERT LITE (UL) INSTRUCTION MANUAL
90
The
fourth parameter
and the
fifth parameter
for each relay set the
pump
“
ON
” and “
OFF
” points, which are entered in
Measurement units P104
. For
pump down
the “
ON
” is set
higher than
“
OFF
”. For
pump up
then “
ON
” is
set
lower than
“
OFF
”. See the appropriate
pump duty,
function
table
(
P212, 222, 232, 242, 252
) for further information.
P213, 223, 233, 243, 253
–
Relay Setpoint 1
This
parameter determines the ‘
ON
’ point of the pump.
P214, 224, 234, 244, 254
–
Relay Setpoint 2
This parameter determines the ‘
OFF
’ poin
t of the pump.
The
sixth parameter
will determine the
service ratio
that will be used to
switch the pump, when
pump duty
selected is a Service Ratio duty.
P215, 225, 235, 245, 255
–
Relay Setpoint 3
This parameter determines the Service Ratio in values of %. See the
appropriate
pump duty
function, table (
P211, 221, 231, 241, 251
), for
further information.
P219, 229, 239, 249, 259
–
Relay Max Rate
This parameter will allow a
pump
to be
switched
at a pre-determined
Rate
of change of Level
, irrespective of th
e “ON” level setpoint P213, 223, 233,
243, 253. Once a pump
relay has been switched “
ON
” by the pre
-determined
Rate of Change
, it will remain energis
ed until the level reaches the “
OFF
”
level setpoint
P214, 224, 234, 244, 254
.
Max. Rate is entered in Measurement Units (P104) per minute and can be
entered as either positive (increasing level) or negative (decreasing level)
values.