23
The blowdown relay can be configured to operate based on a setpoint or based on a water meter input.
When the blowdown relay is selected for programming the following screen will appear.
BLOW
=========================
1 DISABLED
2 *BY TOWER SETPOINT
3 BY MAKEUP VOLUME
4 CHANGE MY NAME
5 SCHEDULED LOCKOUT?
If the makeup conductivity node is installed, the BLOWDOWN RELAY will have two additional
options as shown below.
BLOW
=========================
1 DISABLED
2 BY TOWER SETPOINT
3 BY MAKEUP VOLUME
4 BY CYCLE SETPOINT
5 BY MULTI-SETPOINT
6 CHANGE MY NAME
7 SCHEDULED LOCKOUT?
13.1.2
Disabled
The blowdown relay can be disabled. When a relay is disabled, it will not energize automatically.
From the
RELAY OPTIONS
screen press ―
1” Disabled
to disable the relay.
13.1.3
By Tower Setpoint
To set up the blowdown relay to operate based on a setpoint, select
BY TOWER SETPOINT
. The
following screen will appear.
SETPOINT=
1000 µS
DEADBAND=
10 µS
13.1.4
Setpoint
In the
SETPOINT
screen you will set the
SETPOINT
, the
DEADBAND
and the
BLOWDOWN TIMEOUT
alarm.