Set Mode “H” to 0001 to activate over/under

voltage protection mode. 

Note: over/under 

protection does not work with other functions.

Set Mode “b” to 0000.

Set Mode “I” to adjust the set point for under

voltage cut-off, from 0 to 200 VAC.

Set Mode “d” start up delay on power 

restoration between 000.1 and 999.9 minutes to 

prevent short cycling of connected load.

Set Mode “J” to adjust the set point for over

voltage cut-off from 201 to 300 VAC.

Set mode “L” to adjust the delay before the load 

is restored after an over or under voltage event 

has occurred. Delay from 0.1 to 999.9 minutes.

Quick Start Chart : Over-Under Voltage and Brown Out Protection

 

0000

0000

1

0000

0000

0000

 000.1

To

 999.9

H 0000

To

H 0001

i 0000

To

i 0200

j 0201

To

j 0300

L 000.1

To

L 999.9

0000

0000

0001

 

0000

To

 

0001

Set Mode “A” to 0000 to disable dry contact

control of relay.

0000

A 0000

To

A 0003

SAK-60

Installation Programming Guide

 

Set To: 

Mode 

Adjustment Range 

Adjustment Details

Содержание SAK-60

Страница 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Страница 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Страница 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Страница 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Страница 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Страница 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Страница 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Страница 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...

Отзывы: