Installation Instructions
1.
Device should be installed on DIN rail.
2.
Device must be installed in an enclosure suitable for
the application and environment for which it is being
used. Connected Load shall not exceed 60 amps.
3.
Confirm power is off prior to performing the
installation.
4.
Use the appropriate wire size and type based on the
connected load and torque to the specified ratings.
5.
Connect input and output connections and replace
finger guard covers and restore power.
6.
Confirm power LED is illuminated and proceed to
programming functions.
To Enter Programming Mode
Push “Mode” button one time. There may be a delay up
to one minute while the program finishes the active cycle.
Setup will begin by displaying setting “A 0000”. Each time
the mode button is pressed, the device advances to the
next menu setting. Adjustments to the settings are made
using the UP & DOWN buttons. The mode and settings
are displayed on the LCD screen. The program mode
exits and saves settings after 7 seconds of inactivity.
Set Mode “A” to 0000 to disable dry contact
control of relay.
Set Mode “b” to 0000 to enable load lockout
mode on Generator.
Set Mode “d” to a minimum of 000.2 to
provide 12 second delay after power up.
Warning! Do not apply external voltage to the
dry contact input terminals. This will damage
the SAK-60 and void the warranty.
L1-IN
L2-IN
L1-OUT
L2-OUT
Dry Contact
Input
LCD Display
DOWN Button
UP Button
MODE Button
Auxiliary Terminals
Main Terminals
LI OUT
LI IN
L2 OUT
L2 IN
U 240
SAK-60
Gen-Util LED
MODE
UP
DOWN
GEN-UTIL Load On
Load On LED
Main Terminals
CU7 Copper Conductors Only
10-14 AWG 35 IN. LBS.
8 AWG 40 IN. LBS.,
4-6 AWG 45 IN. LBS.
2-3 AWG 50 IN. LBS.
Auxiliary Terminals
CU7 Copper Conductors Only 12-16 AWG 20 IN. LBS.
Set To:
Mode
Adjustment Range
Adjustment Details
Quick Start Chart : Load Lock-Out on Generator Settings
Quick Start Charts are provided to assist in setting up basic functions. The complete menu is available on
the last pages of this document to assist with advanced functions and provide a better understanding of the
program flow.