Active when Menu Upper Case “C” = 0

Set delay time from 00.01 to 10.00 seconds for F1

under frequency load shed. Default 3 seconds.

Under frequency mode“C 0001” fixed at 3 sec.

Active when Menu Upper Case “C” = 0

Set delay time from 00.01 to 10.00 seconds for F2

under frequency load shed. Default 1.5 seconds.

Under frequency mode“C 0001”  fixed at 1.5 sec.

Under Frequency on Restore Extended Lockout

Upon load restoration, if under frequency event 

occurs within “P” seconds after restoration, this 

extended delay “U” is activated and added to setting 

“O” normal restore delay.

UL Testing Standards and Product Certifications

Construction of control: Independently mounted

Action: Type 1

Over voltage category: OVC III

Pollution degree: PD2

Rated Impulse Voltage: 2500 V

Maximum phase to ground voltage of the supply source: 150 V

Protection against electric shock class: Insulation-encased Class II Equipment

Environmental: IP00

Purpose of control: operating control

Active when Menu Upper Case “C” = 0

Set delay time from 00.01 to 10.00 seconds for F3

under frequency load shed. Default 0.5 seconds.

Under frequency mode“C 0001” fixed at 0.5 sec.

Normal Under Frequency Restore Delay

Set restore time delay from 000.1 to 999.9 minutes

to restore load after under frequency load drop

event has occurred. Normally mirrors Delay G 0000.

Under Frequency During Load Restoration

Set delay time from 0001 to 0010 seconds for

detection of over-load when load is restored. An

extended delay will be executed as set up in “U”.

 1

03.0

0004

 2

02.0

0015

 3

00.5

005.0

 1

00.0

To

 1

10.0

P 0001

To

P 0010

 2

00.0

To

 2

10.0

000.1

To

999.9

 3

00.0

To

 3

10.0

0 000.1

To

0 999.9

SAK-60

Flow Chart Menu continued

  Mode/Default 

Adjustment Range 

Adjustment Details

Содержание SAK-60

Страница 1: ...re displayed on the LCD screen The program mode exits and saves settings after 7 seconds of inactivity Set Mode A to 0000 to disable dry contact control of relay Set Mode b to 0000 to enable load lock...

Страница 2: ...after generator is detected For multiple loads stagger restore times based on priority of loads connected Set Mode C to 0001 to enable pre set under frequency cut off points or set to 0000 to enable u...

Страница 3: ...estoration this extended delay U is activated and added to setting O normal restore delay Time Delay 2 Set delay time from 00 1 to 10 0 seconds for under frequency 2 under frequency load shed Default...

Страница 4: ...event short cycling of connected load Set Mode J to adjust the set point for over voltage cut off from 201 to 300 VAC Set mode L to adjust the delay before the load is restored after an over or under...

Страница 5: ...management under frequency drop of loads when generator detected Active in mode b0001 only Adjust the delay time in minutes before restoring load after generator sine wave has been detected C 0000 to...

Страница 6: ...00Hz follows delay d2 Under frequency mode C 0001 fixed 56 00 Hz Active when Menu C 0000 Under Frequency F3 Set from 50 00 to 60 00 Hz Default setting 52 00Hz follows delay d3 Under frequency mode C 0...

Страница 7: ...VC III Pollution degree PD2 Rated Impulse Voltage 2500 V Maximum phase to ground voltage of the supply source 150 V Protection against electric shock class Insulation encased Class II Equipment Enviro...

Страница 8: ...quency load management The first Mode C 0001 is fixed and the pre set under frequency and delay times cannot be adjusted These values should be suitable for most air cooled applications The second Mod...

Отзывы: