Notes:
- Motor lines connected to contactors (U, V and W) are bridged between set of contactors.
- Unused lines shall be isolated from ground, properly connected among them and secured behind contactors.
27
4.
Depending on voltage requirement, connect lines K1 - K2 - K3 - K4 - K5 - K6 - K7 - K8 and K9 as described
above.
5.
Next to the contactors locate triple voltage power transformer, unplug input (1 wire/line) and plug it as
voltage requirement. 220, 380 and 440V are easily displayed on transformer.
6.
Only for M5 units: Verify and replace Rectifier with corresponding voltage Voltage ranges 300~555V use
Rectifier RH555 UHT 555V~0.75A Voltage ranges 198~270V use Rectifier RB270 UHT 270V~0.75A
7.
Check all connections are tight. Unused motor K lines shall be isolated from ground and properly connected
among them as described in point 3.
8.
Properly place electric box cover.
9.
Remove old voltage tags and marks.
10.
Replace new voltage tags and marks with corresponding new voltage selected.
11.
Remove lockout/tagout and perform all corresponding inspection and testing as described on ASME
B30.16-2.
PWRC and PWRC_M5 Series Triple Voltage Single Speed Electric Chain
Hoist with Power Trolley
1.
Open electric box metal cover.
Содержание PWR M5 Series
Страница 2: ...2 PWR 2 Version 1 0 This page intentionally left blank...
Страница 50: ...50 Wiring Diagram 50 Version 1 0 CONVENTIONAL HOIST WIRING DIAGRAM PWR PWRC...
Страница 51: ...Wiring Diagram 51 Version 1 0 51...
Страница 52: ...52 Wiring Diagram 52 Version 1 0...
Страница 53: ...Wiring Diagram 53 Version 1 0 53...
Страница 68: ...68 Technical Specs 68 Version 1 0 Chain Hoist...
Страница 70: ...70 Technical Specs 70 Version 1 0 Trolley...
Страница 73: ...Technical Specs 73 Version 1 0 73 PWR_M5 ELECTRIC CHAIN...
Страница 80: ...80 PWR 80 Version 1 0 C C A B B A...
Страница 92: ...92 PWRC_M5 92 Version 1 0 T Trolley Motor Width H Trolley minimum Headroom W Width R Trolley D Depth...