Protherm 20 KLO Скачать руководство пользователя страница 17

Supplied By www.heating spares.co  Tel. 0161 620 6677

Mechanical connection of the valve:

 the HCW output from the boiler is connected to the input of the electric-motor-driven 

three-way valve; if the drive motor is inactive (has no voltage), the outputs from the valve to the boiler and to the heating circuit 
must be closed. If a three-way valve is used that has not been supplied by the boiler manufacturer, the electric and water 
connections must act and be oriented exactly as described here!!! 

If the three-way valve used has no switchover contact, the DHW heating may be with the reduced power (if the switch is set to the 
"one flame" icon) and the time of the heating up will be unnecessarily long. The maximum power input of the three-way valve 
can be up to 10 W, the pump's power input up to 100 W: 

4. Description of Controls 

 (Cf. Fig. 3a, 3b) 

Sensors of the emergency thermostat, HCW operation regulators and the HCW pump thermostat are in the boiler body near the 
HCW outlet. The emergency thermostat and the HCW pump thermostat are located on the left hand side, on the service part of the 
control panel. The emergency thermostat is equipped with a reset button and range for temperature setting. The reset button can 
be pressed when the HCW temperature setting has been reduced.  

l

 

The HCW pump thermostat is set to 0°C by a wire locking clamp. The recommended setting is 55°C. 

Next to the thermostat there is the electric fuse. 

 

After the safety elements' response (emergency and flue-gas thermostat), the boiler's operation can only be re-started 
after identifying the reasons for their activation. The boiler must not be operated if the safety elements are disabled 
or replaced with elements different form those specified by the manufacturer. These elements must also be checked 
after each servicing on them. 

5. Boiler Operation 

5.1. Boiler Preparation and Start 

Check water pressure on the boiler pressure gauge. Turn the gas supply valve on. Plug the boiler's power cord into the socket. Set 
the HCW and DHW thermostats to about one half of their ranges. Put the SUMMER/WINTER switch to the WINTER position.  
Put the main switch on. The boiler is ignited and heats up the DHW, then HCW. 

Check the boiler for gas leaks when operated (e.g., by a testing foam) – if any leaks are found (caused by transportation), they 
must be sealed and the check repeated. 

At the end of this procedure, the boiler's power output is checked and, if necessary, adjusted by setting the gas pressure on the gas 
armature. 

Such setting is done by the controls on the combined gas armature (cf. Fig. 5a, 5b), in the order: maximum (i.e., rated), reduced 
(only for 20, 30, 40, 50 KLO). The pressure us measured by a "U" manometer (against the atmospheric pressure). 

Before setting, switch the boiler off and unplug its power cord. Then: 

 

Remove the plugs (A - Fig. 5a, 4a - Fig. 5b) 

 

Unfasten the closing screw (2 - Fig. 5a, 6 - Fig. 5b) of the gas output pressure measurement point and insert the "U" 
manometer's tube.  

Full Power (all types)) 

 

Start the boiler and let it run at full power, heating up either DHW or HCW. The measurement should not be interfered with 
by switching off when the pre-set temperature of water is achieved.  

 

Turn the adjustment screw (B - Fig. 5a, 4b - Fig. 5b) to set the gas pressure 125 mm water column for natural gas, 270 mm 
water column for LPG. 

The gas pressure is increased when the screw is turned clockwise. 

Reduced Power (only 20, 30, 40, 50 KLO) 

 

Set the power switch ("one flame" or "two flames" icon) to reduced power ("one flame"); 

 

Turn the screw (C) counter-clockwise to set the left extreme position – for minimum power output. 

 

Turn the knob (D) on the automatic part: a 55 mm water column for natural gas, 130 mm water column for LPG. 

 

16

Содержание 20 KLO

Страница 1: ...By www heating spares co Tel 0161 620 6677 Instructions for Use and Installation of Cast Iron Boilers PROTHERM 20 30 40 50 60 KLO BEAR Version Protherm s r o ltd Pplk Plju ta 45 909 01 Skalica Slovak...

Страница 2: ...ig 3b Vertical Control Panel 11 Fig 4a Electric Wiring Diagram of PROTHERM 60 KLO 18 Fig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO 18 Fig 5a Regulation elements of SIT 843 combined gas ar...

Страница 3: ...Do not remove or damage any labels or markings on the boiler 9 The boiler complies with all Czech applicable regulations If it is to be used in another country deviations in the regulations have to b...

Страница 4: ...ted if the valve s motor is not active gets no voltage The boiler s manufacturer supplies both DHW reservoirs 100 150 200 l and suitable three way distribution valves l DHW heating takes preference ov...

Страница 5: ...onnection Dimensions 1 Control panel 2 HCW pressure measuring point 3 HCW temperature measuring point 4 Boiler cast iron body 5 Combined gas armature 6 Water filling and discharging 7 Burner plate dis...

Страница 6: ...the required and actual parameters i e the state of the boiler and the heating circuit the gas pipe leading out of the armature is part of the burner plate with 2 to 6 nozzles one per each burner tube...

Страница 7: ...3 Chimney flange 4 Flue gas duct with draft dampener 5 SKKT chimney draft control system 6 Outgoing HCW 7 Gas supply 8 Cast iron elements 9 Incoming HCW 10 Combustion chamber 11 Secondary air supply 1...

Страница 8: ...ce is solved by ventilation openings of sufficient size Gas appliances with flue gas removal to chimneys must not be in rooms in which negative air pressure is created by ventilation fans 3 4 Flue Gas...

Страница 9: ...pes so that the pipe fixtures on the boiler should not be affected by any pressures or tensions The fixtures on the boiler have outside male threads l Closing valves are recommended to be installed on...

Страница 10: ...gas piping i e electricity supply to the boiler must be stopped in addition to using the boiler switch e g by unplugging b Stopping the boiler whenever flammable or explosive vapours appear even if t...

Страница 11: ...such defects may be caused by not igniting the flame no gas or the chimney draft control system if there is none or too low a draft or emergency thermostat if the HCW temperature is above 100 C may h...

Страница 12: ...lements flue gas and emergency temperature thermostats disabled or replaced with elements different from those specified by the manufacturer Users are not allowed to tamper with the safety elements He...

Страница 13: ...regulator If the boiler does not ignite and the defect indicator is off the operation is stopped due to one of the operational reasons we have just described the heating will automatically start agai...

Страница 14: ...and persons under the influence of drugs or otherwise incapable must be prevented from operating the boiler 7 2 Quality Compliance The boiler s quality compliance is provided by and checked within the...

Страница 15: ...olted on a palette Do not let any forces act on the casing when handling or when storing the boiler For handling without a palette the base can be used cf Chapter 2 For storage normal conditions have...

Страница 16: ...eedle on the boiler pressure gauge 3 9 Electrical Connections of Boiler The electrical installation cabinet and the service part of the control panel are accessible when the top panel of the boiler is...

Страница 17: ...nufacturer These elements must also be checked after each servicing on them 5 Boiler Operation 5 1 Boiler Preparation and Start Check water pressure on the boiler pressure gauge Turn the gas supply va...

Страница 18: ...rocedure must be followed Only authorised service centres are allowed to carry out the conversion The following steps are to be followed 1 Dismount the burner from the boiler 2 Replace the nozzles wit...

Страница 19: ...ig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO HV Main switch PO1 Electrical fuse SP Power stage switch TL1 RESET button DT1 Emergency state indicator HT Emergency temperature thermostat TS...

Страница 20: ...1 620 6677 Fig 5a Regulation elements of SIT 843 combined gas armature for boilers 20 30 40 50 KLO a Input b Output 1 Setting screw for maximum 2 Setting screw for minimum Fig 5b Regulation elements o...

Страница 21: ...2 3 Flue gas removal manner to chimney to chimney diam outlet mm 130 130 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 13 3 19 8 Effi...

Страница 22: ...ue gas removal manner to chimney to chimney to chimney diam outlet mm 150 180 180 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 26 6 3...

Отзывы: