Protherm 20 KLO Скачать руководство пользователя страница 10

Supplied By www.heating spares.co  Tel. 0161 620 6677

Sufficient clearance space must be provided around the boiler to enable manipulation of the boiler and its accessories, both when 
being installed and during operation. 

The boiler is put on the floor (or a special base plate). The floor must have at least usual load capacity and must not be slippery. 
The area at the boiler must be dry-cleaned (such as vacuum cleaning). The boiler must not stand on a flammable base – if the floor 
is flammable, a special flameproof, thermally insulating base plate must be used; its dimensions must be, in all directions, at least 
100 mm larger than the floor projection of the boiler. 

The boiler with the casing needs a doorframe clearance width of at least 65 cm. 

The following clearance distances are prescribed: 

–  100 mm from flameproof to moderately flammable materials; 

–  200 mm from flammable materials (such as chipboard, polyurethane, polystyrene, polyethylene, expanded PVC, synthetic 
fibre, cellulose, asphalt board, rubber, etc.). 

The boiler is designed for operation in a normal environment (temperatures b5 and +40°C, humidity up to 85%, 
depending on the temperature). 

The boiler must not be installed in rooms with a bathtub, or in bathrooms, washing areas and shower rooms, in zone 
0, 1 or 2. It cannot be installed in zones 3 in which water streams are used for cleaning (such as bathhouses, shower 
and washing rooms in schools, factories, sporting facilities, public facilities, etc.)

 

If the boiler is installed in allowed zones, the relevant standard also requires adequate protection form electric shock. 

 

 

 

The boiler must not be installed in an environment in which the burner tubes could be clogged with impurities or biological 
factors (such as small rodents, etc.). 

 

 

In practice, situations may appear in which the users must apply necessary precautions: 

a)

 

Preventing the boiler from switching on (also accidental) when inspecting the chimney, flue-gas duct, water and gas 
piping – i.e., electricity supply to the boiler must be stopped in addition to using the boiler switch (e.g., by unplugging); 

b)

 

Stopping the boiler whenever flammable or explosive vapours appear (even if temporarily) – such as vapours of 
flooring glue, paints when surface finishing, gas leaks, etc.); 

c)

 

If it is necessary to discharge water from the heating system, it must not be dangerously hot; 

d)

 

If there is a stoppage of the heating system (boiler or circuit) which might lead to water leak from the boiler exchanger, 
or if the exchanger is filled with ice, no attempts to start the boiler should be made until normal operating conditions 
prevail. 

3.9. Electric Connections of Boiler 

Electric connection of the boiler to the grid is by three-wire flex and plug. The socket for the plug must comply with the relevant 
standard and have the grounding pin (connected to a PE or PEN cable (yellow-green). 

The boiler must be connected to the protective grounding wire; the plug in the socket must always be accessible without obstacles. 

Use of adaptor plugs, extension cords, etc. is prohibited. The boiler is protected by a tube fuse (T 1.6 A / 250 V), installed under 
the front cover panel.  

Only a person with adequate electrical-engineering qualifications can be allowed to install the socket and the thermostat 
(thermostat installation requires utilization of the boiler's internal electric cabling); the same requirements apply to servicing the 
electric part.  

 

Before any work commences on the electric part, the boiler must be unplugged.

 

 

 

Only no-voltage thermostats or regulators can be used for regulating the boiler, i.e., they must not bring in any foreign 
voltage. A specialised service centre should assess suitability of a particular regulator. 

3.10. Regulator Connection 

There is a terminal board in the boiler, which is under the control panel. A room thermostat with no-voltage contact switch is 
connected to the boiler by a power cable. If a regulator requiring 230 V supply (bimetal with warm-up resistor) is used, it must be 
connected by a three-wire power cable to the boiler. The boiler manufacturer is able to supply suitable regulators, if required.  

 

9

Содержание 20 KLO

Страница 1: ...By www heating spares co Tel 0161 620 6677 Instructions for Use and Installation of Cast Iron Boilers PROTHERM 20 30 40 50 60 KLO BEAR Version Protherm s r o ltd Pplk Plju ta 45 909 01 Skalica Slovak...

Страница 2: ...ig 3b Vertical Control Panel 11 Fig 4a Electric Wiring Diagram of PROTHERM 60 KLO 18 Fig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO 18 Fig 5a Regulation elements of SIT 843 combined gas ar...

Страница 3: ...Do not remove or damage any labels or markings on the boiler 9 The boiler complies with all Czech applicable regulations If it is to be used in another country deviations in the regulations have to b...

Страница 4: ...ted if the valve s motor is not active gets no voltage The boiler s manufacturer supplies both DHW reservoirs 100 150 200 l and suitable three way distribution valves l DHW heating takes preference ov...

Страница 5: ...onnection Dimensions 1 Control panel 2 HCW pressure measuring point 3 HCW temperature measuring point 4 Boiler cast iron body 5 Combined gas armature 6 Water filling and discharging 7 Burner plate dis...

Страница 6: ...the required and actual parameters i e the state of the boiler and the heating circuit the gas pipe leading out of the armature is part of the burner plate with 2 to 6 nozzles one per each burner tube...

Страница 7: ...3 Chimney flange 4 Flue gas duct with draft dampener 5 SKKT chimney draft control system 6 Outgoing HCW 7 Gas supply 8 Cast iron elements 9 Incoming HCW 10 Combustion chamber 11 Secondary air supply 1...

Страница 8: ...ce is solved by ventilation openings of sufficient size Gas appliances with flue gas removal to chimneys must not be in rooms in which negative air pressure is created by ventilation fans 3 4 Flue Gas...

Страница 9: ...pes so that the pipe fixtures on the boiler should not be affected by any pressures or tensions The fixtures on the boiler have outside male threads l Closing valves are recommended to be installed on...

Страница 10: ...gas piping i e electricity supply to the boiler must be stopped in addition to using the boiler switch e g by unplugging b Stopping the boiler whenever flammable or explosive vapours appear even if t...

Страница 11: ...such defects may be caused by not igniting the flame no gas or the chimney draft control system if there is none or too low a draft or emergency thermostat if the HCW temperature is above 100 C may h...

Страница 12: ...lements flue gas and emergency temperature thermostats disabled or replaced with elements different from those specified by the manufacturer Users are not allowed to tamper with the safety elements He...

Страница 13: ...regulator If the boiler does not ignite and the defect indicator is off the operation is stopped due to one of the operational reasons we have just described the heating will automatically start agai...

Страница 14: ...and persons under the influence of drugs or otherwise incapable must be prevented from operating the boiler 7 2 Quality Compliance The boiler s quality compliance is provided by and checked within the...

Страница 15: ...olted on a palette Do not let any forces act on the casing when handling or when storing the boiler For handling without a palette the base can be used cf Chapter 2 For storage normal conditions have...

Страница 16: ...eedle on the boiler pressure gauge 3 9 Electrical Connections of Boiler The electrical installation cabinet and the service part of the control panel are accessible when the top panel of the boiler is...

Страница 17: ...nufacturer These elements must also be checked after each servicing on them 5 Boiler Operation 5 1 Boiler Preparation and Start Check water pressure on the boiler pressure gauge Turn the gas supply va...

Страница 18: ...rocedure must be followed Only authorised service centres are allowed to carry out the conversion The following steps are to be followed 1 Dismount the burner from the boiler 2 Replace the nozzles wit...

Страница 19: ...ig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO HV Main switch PO1 Electrical fuse SP Power stage switch TL1 RESET button DT1 Emergency state indicator HT Emergency temperature thermostat TS...

Страница 20: ...1 620 6677 Fig 5a Regulation elements of SIT 843 combined gas armature for boilers 20 30 40 50 KLO a Input b Output 1 Setting screw for maximum 2 Setting screw for minimum Fig 5b Regulation elements o...

Страница 21: ...2 3 Flue gas removal manner to chimney to chimney diam outlet mm 130 130 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 13 3 19 8 Effi...

Страница 22: ...ue gas removal manner to chimney to chimney to chimney diam outlet mm 150 180 180 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 26 6 3...

Отзывы: