Protherm 20 KLO Скачать руководство пользователя страница 16

Supplied By www.heating spares.co  Tel. 0161 620 6677

The following instructions are for specialised professionals only. Together with 

the "Instructions for Use" and the "Service Booklet," technical instructions 

for installation, setting and maintenance are provided. 

Numbers and headings of the chapters are the same as in the "Instructions for Use" 

3. Boiler Assembly 

When servicing the boiler that is plugged into the electrical grid (even if the main switch is off), all safety precautions for work on 
electric equipment must be adhered to. 

The boiler casing can be dismounted. The top and front cover panels are removable, fixed by spring clamps in their corners. The 
front panel is removed by pulling forward, the top panel by pulling upward. Removal requires overcoming the force of the spring 
clamps. The remaining casing panels are fixed to the body by pins and bolts. All parts of the casing are connected to the boiler 
electrical installation by protective wires. 

 

 

The pipe connections of the boiler (water or gas) should never be used as manipulation handles!!! 

3.7. Heating System – Properties and Filling 

The emergency thermostat settings must be adjusted according to the type of the expansion vessel used (closed or open): for open 
to 95°C, for closed to 110°C. 

The HCW regulator must be pre-set to max. 85°C for open vessels, to prevent undesirable overlapping of temperature ranges 
caused by value tolerances and adversary responses of the emergency thermostat. 

The range of the HCW operation regulator is done by a locking wire clamp, which is in the bottom part of the regulator's knob.  
The clamp is accessible when the knob is taken off the thermostat shaft. The setting must be verified by an operational test. 

After filling the heating system with water, purging and setting the pressure expansion vessel (if there is one), the final HCW 
pressure value is set by the red needle on the boiler pressure gauge. 

3.9. Electrical Connections of Boiler 

The electrical installation cabinet and the service part of the control panel are accessible when the top panel of the boiler is 
removed. The front part of the cabinet consists of the control panel, fixed by two screws. When the panel is tilted forward, the 
terminal board for connection of eternal equipment becomes accessible. The panel remains connected to the boiler by the wires 
and tubes of the measurement devices. 

If the boiler is to be operated with a room thermostat, the jumper between the contacts on the terminal board is removed; 
otherwise the jumper must remain on the board. 

A room thermostat is connected by a power cable to contacts No. Pr 19 and 20 – the recommended cross-section of the cable 
wires is between 0.5 and 1.5 mm

2

.  

 
 

The no-voltage rule must be fulfilled by the room thermostat regulator!  

If a bimetal regulator is used, which requires 230 V supply for its function, then the phase (L) and null (N) contact of the regulator 
are connected to Pr 19 and N contacts on the boiler terminal board; the output contact of the regulator is connected to Pr 20 on the 
boiler terminal board. The minimum allowed load of the regulator's contacts should be 230 V A.C. /2A (inductive load). 

Pump connection 

– if the load is higher than the value allowed by the fuse of the boiler, an additional switching element 

(contactor) must be used. 

Connections of parts for cooperation with external DHW reservoir

 (i.e., electric-motor-driven three-way valve and reservoir 

thermostat) – they have to be connected to the boiler terminal board: the middle switching contact of the reservoir is connected to 
TbC (No. 6). The outside contacts are connected to Tb1 and Tb2 (No. 7 and 8) so that TbC and Tb1 have conductive connection 
when the DHW is cold in the reservoir. The three-way valve drive is connected to N (No. 10) and L (No. 11) contacts; the 
switching contact of the three-way valve (only for 20, 30, 40, 50 KLO) is connected to W1, W2 (No. 12, 13). The contact must be 
interconnected when the valve's drive has no voltage. 

 

 

15

Содержание 20 KLO

Страница 1: ...By www heating spares co Tel 0161 620 6677 Instructions for Use and Installation of Cast Iron Boilers PROTHERM 20 30 40 50 60 KLO BEAR Version Protherm s r o ltd Pplk Plju ta 45 909 01 Skalica Slovak...

Страница 2: ...ig 3b Vertical Control Panel 11 Fig 4a Electric Wiring Diagram of PROTHERM 60 KLO 18 Fig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO 18 Fig 5a Regulation elements of SIT 843 combined gas ar...

Страница 3: ...Do not remove or damage any labels or markings on the boiler 9 The boiler complies with all Czech applicable regulations If it is to be used in another country deviations in the regulations have to b...

Страница 4: ...ted if the valve s motor is not active gets no voltage The boiler s manufacturer supplies both DHW reservoirs 100 150 200 l and suitable three way distribution valves l DHW heating takes preference ov...

Страница 5: ...onnection Dimensions 1 Control panel 2 HCW pressure measuring point 3 HCW temperature measuring point 4 Boiler cast iron body 5 Combined gas armature 6 Water filling and discharging 7 Burner plate dis...

Страница 6: ...the required and actual parameters i e the state of the boiler and the heating circuit the gas pipe leading out of the armature is part of the burner plate with 2 to 6 nozzles one per each burner tube...

Страница 7: ...3 Chimney flange 4 Flue gas duct with draft dampener 5 SKKT chimney draft control system 6 Outgoing HCW 7 Gas supply 8 Cast iron elements 9 Incoming HCW 10 Combustion chamber 11 Secondary air supply 1...

Страница 8: ...ce is solved by ventilation openings of sufficient size Gas appliances with flue gas removal to chimneys must not be in rooms in which negative air pressure is created by ventilation fans 3 4 Flue Gas...

Страница 9: ...pes so that the pipe fixtures on the boiler should not be affected by any pressures or tensions The fixtures on the boiler have outside male threads l Closing valves are recommended to be installed on...

Страница 10: ...gas piping i e electricity supply to the boiler must be stopped in addition to using the boiler switch e g by unplugging b Stopping the boiler whenever flammable or explosive vapours appear even if t...

Страница 11: ...such defects may be caused by not igniting the flame no gas or the chimney draft control system if there is none or too low a draft or emergency thermostat if the HCW temperature is above 100 C may h...

Страница 12: ...lements flue gas and emergency temperature thermostats disabled or replaced with elements different from those specified by the manufacturer Users are not allowed to tamper with the safety elements He...

Страница 13: ...regulator If the boiler does not ignite and the defect indicator is off the operation is stopped due to one of the operational reasons we have just described the heating will automatically start agai...

Страница 14: ...and persons under the influence of drugs or otherwise incapable must be prevented from operating the boiler 7 2 Quality Compliance The boiler s quality compliance is provided by and checked within the...

Страница 15: ...olted on a palette Do not let any forces act on the casing when handling or when storing the boiler For handling without a palette the base can be used cf Chapter 2 For storage normal conditions have...

Страница 16: ...eedle on the boiler pressure gauge 3 9 Electrical Connections of Boiler The electrical installation cabinet and the service part of the control panel are accessible when the top panel of the boiler is...

Страница 17: ...nufacturer These elements must also be checked after each servicing on them 5 Boiler Operation 5 1 Boiler Preparation and Start Check water pressure on the boiler pressure gauge Turn the gas supply va...

Страница 18: ...rocedure must be followed Only authorised service centres are allowed to carry out the conversion The following steps are to be followed 1 Dismount the burner from the boiler 2 Replace the nozzles wit...

Страница 19: ...ig 4b Electric Wiring Diagram of PROTHERM 20 30 40 50 KLO HV Main switch PO1 Electrical fuse SP Power stage switch TL1 RESET button DT1 Emergency state indicator HT Emergency temperature thermostat TS...

Страница 20: ...1 620 6677 Fig 5a Regulation elements of SIT 843 combined gas armature for boilers 20 30 40 50 KLO a Input b Output 1 Setting screw for maximum 2 Setting screw for minimum Fig 5b Regulation elements o...

Страница 21: ...2 3 Flue gas removal manner to chimney to chimney diam outlet mm 130 130 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 13 3 19 8 Effi...

Страница 22: ...ue gas removal manner to chimney to chimney to chimney diam outlet mm 150 180 180 Min required draft in chimney Pa 2 Flue gas temperature natural gas C 100 LPG C 95 Weight flowrate flue gas g s 26 6 3...

Отзывы: