93-520-20 Issue 3.3
Page 41 of 60
CirrusPro Engineer’s Manual
3.4.13 Historic Graph
The Historic Graph shows a period of about three
days, with about 10 days stored. The amount of
data is dependent on what has happened during the
recording period. The amount of data stored
increases during fire and pre alarm events.
3.4.14 Security Code
On opening this screen, the display shows 0. Use +
and – to increase or decrease the value and Select
(Sel) to add another digit. Use no more than 9 digits.
Note that the first digit cannot be 0.
When the required code is displayed press Accept to
immediately update the unit. It is very important to log
this code as it cannot be extracted from the unit.
Pressing Exit leaves this display without changing the
code.
3.4.15 Clear Log
Select Yes or No:
Yes, to clear the event log after which a confirmation
message appears for a short time.
No, to exit and return to the Main Options Menu.