93-520-20 Issue 3.3
Page 32 of 60
CirrusPro Engineer’s Manual
3.4
Commissioning by Display
The units can be commissioned using the internal or remote displays, if connected. Most of the PC
functions are available from display units and are described in detail in the PC commissioning
sections.
The text at the bottom of the display corresponds to the push buttons below the display. By holding
down a button, its function will auto-repeat.
On powering up, the display shows the display software version number for a short time, then the
Logo Menu. The unit searches the network for detectors and displays the number found. If, during
operation, a detector is disconnected this indicated as shown.
3.4.1 Network setting display software V 1.10
Pressing Menu lists the units found on the network. The Up and Down keys move between the units.
0 1 2 Buttons for code entry.
From this Menu, to enter the Network Setup menu,
enter the sequence 112020 using the buttons from
the left where the far left button is 0 and Down and
Up are 1 and 2 respectively.