Configuring Modbus/BSAP
RLXIC-SV
♦
Intelligent Cellular
User Manual
RadioLinx Intelligent Cellular Serial Modem for the Verizon Wireless CDMA Network
ProSoft Technology, Inc.
Page 85 of 146
May 29, 2009
With names instead of IP addresses for the Address List, the host modem will
query the DNS server for the current IP address assigned to the specific name of
a remote modem to send a message corresponding to the ID.
When you use names instead of IP addresses, to ensure your modems are
updated quickly with the correct IP addresses for the names, you will want to set
the DNS settings as well. In AceManager, select
DNS
.
Configure *DNSUSER to the same IP address as the IP Manager
(*IPMANAGER1). If your modems have dynamic IP addresses, and not static
(the IP address can change when it is powered up), configure *DNSUPDATE to a
low interval to allow frequent updates.
9.3
Configuring the Remote RLXIC-SVs for Modbus with UDP
This section covers standard Modbus settings for the RLXIC-SV at the remote
unit, variations may need additional commands.
9.3.1 Configure the ports
In AceManager, select
M
ISC
in the side menu.