Ladder Logic
MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 42 of 225
ProSoft Technology, Inc.
July 8, 2011
5
Click
N
EXT
to continue.
6
Select the
Requested Packet Interval
value for scanning the I/O on the
module. This value represents the minimum frequency at which the module
will handle scheduled events. It should not be set to less than 1 millisecond.
Values between 5 and 10 milliseconds should work with most applications.
7 S
AVE
the module. Click
OK
to dismiss the dialog box. The
Controller
Organization
window now displays the module's presence. The following
illustration shows the
Controller Organization
window:
8
Copy the
user-defined data types
from the sample program.
9
Copy the
controller tags
from the sample program.
10
Copy the ladder rungs from the sample program.
11
Save and download (page 36) the new application to the controller and place
it in RUN mode.