![ProSoft Technology inRax MVI69-PDPMV1 Скачать руководство пользователя страница 131](http://html1.mh-extra.com/html/prosoft-technology/inrax-mvi69-pdpmv1/inrax-mvi69-pdpmv1_user-manual_1618985131.webp)
MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
Mailbox Messaging
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 131 of 225
July 8, 2011
4.5.4 DPV1 Class 1-Related Error Codes
Related mailbox commands:
Class 1 Read (FB_APPL_MSAC1_READ)
Class 1 Write (FB_APPL_MSAC1_WRITE)
Possible error codes in Message Data word "Return Code".
Return Code
Name
Meaning
0000h
DPMC_ERR_M_NO_INFO
No additional information
0003h
DPMC_ERR_M_MEM_ALLOC
Internal memory allocation error
0004h
DPMC_ERR_M_L2_REQ
Unknown opcode in the configuration
0005h
DPMC_ERR_M_INVALID_PAR
Invalid parameter in user request
0007h
DPMC_ERR_M_NOT_IN_DATA
Slave is not in DataExchange (thus no DP-V1 request can
exist)
0012h
DPMC_ERR_M_REQ_ACTIVE
A request is already active
0018h
DPMC_ERR_M_NOT_ALLOWED
Internal DPMC module not initialized correctly
0021h
DPMC_ERR_M_CLOSED
Internal DPMC instance no longer exists
0022h DPMC_ERR_M_STOPPED
Internal
DPMC instance has already been stopped
0023h
DPMC_ERR_M_STARTED
Internal DPMC instance has already been started
0024h
DPMC_ERR_M_STATE_UNKNOWN
Internal DPMC instance has entered an undefined state
002Fh
DPMC_ERR_M_SLAVE_NOT_FOUND
Slave does not respond
0031h
DPMC_ERR_M_TIMEOUT
Active request terminated with timeout
0034h
DPMC_ERR_M_INVALID_LEN
Invalid length in user request
0035h
DPMC_ERR_M_REQ_NEG
Negative indication from lower layer
0036h
DPMC_ERR_M_REQ_RE
Message frame format error in response
0037h
DPMC_ERR_M_REQ_WITHDRAW
Request was recalled
0038h
DPMC_ERR_M_REQ_NOT_FOUND
Associated request block not found
0040h
DPMC_ERR_M_MM_FE
Format error in request frame
0041h DPMC_ERR_M_MM_NI
Function
not
implemented
0042h DPMC_ERR_M_MM_AD
Access
denied
0043h DPMC_ERR_M_MM_EA
Area
too
large
0044h
DPMC_ERR_M_MM_LE
Data block length too large
0045h
DPMC_ERR_M_MM_RE
Format error in response frame
0046h DPMC_ERR_M_MM_IP
Invalid
parameter
0047h DPMC_ERR_M_MM_SC
Sequence
conflict
0048h DPMC_ERR_M_MM_SE
Sequence
error
0049h DPMC_ERR_M_MM_NE
Area
non-existent
004Ah
DPMC_ERR_M_MM_DI
Data incomplete or incorrect
004Bh
DPMC_ERR_M_MM_NC
Master parameter set not compatible
004Ch
DPMC_ERR_M_S7_XA
PROFIBUS error for DP-V1 (NRS-PDU received)
004Dh DPMC_ERR_M_S7_XR
004Eh DPMC_ERR_M_S7_XW