![ProSoft Technology inRax MVI69-PDPMV1 Скачать руководство пользователя страница 173](http://html1.mh-extra.com/html/prosoft-technology/inrax-mvi69-pdpmv1/inrax-mvi69-pdpmv1_user-manual_1618985173.webp)
MVI69-PDPMV1
♦
CompactLogix or MicroLogix Platform
Reference
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 173 of 225
July 8, 2011
Byte Offset
Start End Name
Description
108 109 Module alarm IND
receive counter
Number of spontaneous alarm messages received
from slave.
110 111 Module alarm CON
receive counter
Number of confirmation messages received from
slaves indicating that the slave received the
confirmation message from the MVI69-PDPMV1
module
112 113 Reserved
114 115 Reserved
116 117 Module backplane
read count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane read data transfers
118 119 Module backplane
write count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane write data transfers
120 121 Module backplane
error count
Rollover counter of the number of MVI69-PDPMV1
to processor backplane data transfers that have
failed
122
123
File Error Word
This is bitmapped value that indicates which files are
not present.
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Problem with WATTCP.CFG file
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR
LED on the module will be illuminated.
124 149 Not
used
150 151 In mailbox queue
count
Number of message in the in mailbox queue
152 153 Out mailbox queue
count
Number of message in the out mailbox queue
154
155
Alarm queue count Number of message in the alarm queue
156 157 Last out mailbox
message ID
processed from
output image
Last out mailbox message ID processed from output
image
158 159 Current in mailbox
control index
Current in mailbox control index
160 161 Current alarm
control index
Current alarm control index
162
483
Reserved
Reserved for future use