6.1.1 General
Specifications
Single-slot,
1769
backplane-compatible
The module is recognized as an Input/Output module and has access to
processor memory for data transfer between processor and module.
Ladder Logic is used for data transfer between module and processor. A
sample ladder file with AOI is included.
Configuration data obtained from configuration text file downloaded to
module. A sample configuration file is included.
Supports CompactLogix and MicroLogix 1500 LRP processors with 1769 I/O
bus capability and at least 800 mA of 5 Vdc backplane current.
CIPConnect
®
enabled. Module supports communications with ProSoft
Configuration Builder and FDT comDTM via Ethernet routing using Rockwell
Automation Ethernet interface.
CIPConnect
®
currently supports only L32E and L35E CompactLogix
processors.
6.1.2 Hardware
Specifications
Specification Description
Dimensions
Standard 1769 single-slot module
Current Load
800 mA max @ 5 Vdc
Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)
Operating Temp.
0°C to 60°C (32°F to 140°F)
Storage Temp.
-40°C to 85°C (-40°F to 185°F)
Relative Humidity
5% to 95% (with no condensation)
LED Indicators
Power and Module Status
Application Status
Serial Port Activity
Serial Activity and Error Status
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
CIPconnect
®
Ethernet routing when using 1769-
L32E or 1769-L35E
Shipped with Unit
RJ45 to DB-9M cables for each port
6-foot RS-232 configuration cable