P_MAZ_0001_SW
2
1
Fig. 12: Standard installation
1
Main line
2
Storage tank
Symbol
Explanation
Symbol
Explanation
Injection valve
Multifunctional valve
Manometer
Relief valve (alterna‐
tively a multifunction
valve can be used)
Metering pump
Level switch
Foot valve with filter
meshes
CAUTION!
If you do not connect any flushing equipment, then you must
ensure that no dust and no foreign bodies can enter through
the top hose nozzles!
Otherwise this may result in damage to the liquid end. For
example, fit a sealing stopper (order no. 359585).
The leakage liquid is drained off via the flushing collar and a hose nozzle,
without other parts of the liquid end coming into contact with the medium.
1.
Connect a hose to the lower hose nozzle.
2.
Route the hose into a collection vessel for the leakage liquid.
CAUTION!
–
A flushing equipment must be connected when using
very aggressive or toxic media or when using media with
a poor lubricating effect.
–
The flushing agent must be compatible with the feed
chemical and the wetted materials of the liquid end.
–
The flushing medium pressure must not exceed 0.5 bar.
Connect the flushing equipment to the hose nozzles via two hoses.
Standard installation
Symbols for the components
Route the leakage liquid drainage line
Connecting the flushing equipment