6.5.2.4
[Remote control - pause, analog I/O]
Selection of the UV lamp control: in the setting
[Internal UV lamp control], the control regulates the UV lamp to a
constant UV sensor signal. In external UV lamp control via a 4 ...
20 mA input signal, the UV system controls in proportion to the
input value using a P control algorithm.
In the
[External UV lamp control] control mode, the nominal dose of
the
[Lamp control automatic mode power stage 1] setting is used.
Power stage 2 is deactivated in this control mode.
Pause
[YES] or [NO]. Analogue output (0 ... 20 mA or 4 ... 20 mA)
for the processed UV sensor signal.
A1206
Menu
Internal or remote control
INT
NO
Control INT/EXT Setpoint lamp power
Pause contact active: YES/NO
Analogue output: 0/4 - 20 mA
Home
4
F6-EXT
F1-INT
Fig. 33: [Remote control - pause, analog I/O]
A2832
Menu
UV dose calculation
INT
UVT-10:
95 %
Home
Flow level 1:
Back
25.00 m
3
/h
Flow level 2:
10.00 m
3
/h
m
3
/h
GPM
m
3
/h
Fig. 34: UV dose calculation internally [INT]
1.
Use the
[TAB] key to select the value to be adjusted.
You can choose between the
[m
3
/h] and [gpm] display units for the
flow
UV dose calculation internally
[INT]
Control
42