B0954
Fig. 9: PVCU connector (Ø63 mm)
11. Connect a PVCU pipe (Ø63 mm) to the PVCU connector
(Ø63 mm) of the system and lead it outside. The pipe must
initially rise a minimum of 1 metre upwards before the first
bend is connected.
Contact the supplier if the line will have more than 3 bends
and is longer than 10 metres.
Route the line outside so that nothing can fall into the line.
12. Make sure that the PVCU pipe (Ø63 mm) routed outside
complies with the regulations.
Always route the PVCU discharge line upwards. Do not allow
any part of the PVCU discharge line to point downwards.
Ensure that the PVCU discharge line does not have more
than 3 bends.
The maximum permissible length of the PVCU discharge line
is 10 metres.
CAUTION!
Danger of vaporisation
Never connect this line to the exhaust air line for
the hydrogen.
Installation and assembly