INSTALLATION RECOMMENDATIONS
If possible, position the gascooler preferably above the entry point of the liquid into the liquid receiver, to help the condensate flow
away by gravity (subcritical running).
If the unit is to be mounted on a roof, roof structure has to be strong enough to support total weight of the gascooler without
bending.
AREA OF INSTALLATION
When installing multiple units,a space of 1200mm should be allowed around the condensers to prevent exhaust air recirculation. For
special installation, please contact the Manufacturer.
For Horizontal condensers frame mounted:
Free space bottom the condenser > 590 mm
For Vertical condensers frame mounted:
Space (Exchanger <-> Wall) height of the heat exchanger
For special installation, please consult us.
REFRIGERATION NETWORK CONNECTION
General information
B
EFORE ANY WORK IS DONE ON THE REFRIGERATION CIRCUIT
,
THE HOLDING CHARGE MUST BE REMOVED
(NITROGEN).
The piping used (copper CuFe2P or stainless steel 304L) must be of refrigeration quality in accordance with PED 2014/68/UE.
All piping must be correctly supported and fixed and should in no case be allowed to restrict the piping of the gascooler.
Specific connection TENOR MS, TENOR MD, ALTO MD, SOPRANO MD, ADAGIO MD
TENOR MS
TENOR MD
ALTO MD, SOPRANO MD, ADAGIO MD