AGP-3300 Series User Manual
3-4
• Be sure that the ambient operation temperature and the ambient humidity are
within their designated ranges. (Ambient operation temperature: 0 to 50°C, Ambi-
ent humidity: 10 to 90%RH, Wet bulb temperature: 39°C max.) When installing
the AGP on the panel of a cabinet or enclosure, “Ambient operation temperature”
indicates both the panel face and cabinet or enclosure’s internal temperature.
• Be sure that heat from surrounding equipment does not cause the AGP to exceed
its standard operating temperature.
• When installing the AGP in a slanted panel, the panel face should not incline
more than 30°.
• When installing the AGP in a slanted panel, and the panel face inclines more than
30°, the ambient temperature must not exceed 40 °C. You may need to use
forced air cooling (fan, A/C) to ensure the ambient operating temperature is 40 °C
or below.
• When installing the AGP vertically, position the unit so that the Power Input Termi-
nal Block is also vertical.
Panel
face
Cabinet
interior
30° or less