AGP-3300 Series User Manual
2-8
2.3
Interface Specifications
2.3.1
Serial Interfaces
AGP-3300/3301 Series
Serial Interface (COM1)
This interface is used to connect an RS-232C or RS-422 (serial)
*1
cable. A D-sub 9-pin plug connector is
used.
• The AGP unit’s serial port is not isolated. When the host (PLC) unit is also not
isolated, be sure to connect the #5 SG (Signal Ground) terminal to reduce the risk
of damaging the RS-232C/RS-422 circuit.
• Inside the AGP unit, the SG (Signal Ground) and FG (Frame Ground) terminals
are connected.
• When connecting an external device to the AGP using the SG terminal, be sure
to check that no short-circuit loop is created when you setup the system.
Pin
Arrangement
Pin
No.
RS-232C
Signal
Name
Direction
Meaning
1
CD
Input
Carrier Detect
2
RD(RXD)
Input
Receive Data
3
SD(TXD)
Output
Send Data
4
ER(DTR)
Output
Data Terminal Ready
5
SG
-
Signal Ground
6
DR(DSR)
Input
Data Set Ready
7
RS(RTS)
Output
Request to Send
8
CS(CTS)
Input
Send Possible
9
CI(RI)
/VCC
Input/-
Called status d5V±5% Out-
put 0.25A
*2
Shell
FG
-
Frame Ground (Common with SG)
Pin
Arrangement
Pin
No.
RS-422
Signal
Name
Direction
Meaning
1
RDA
Input
Receive Data A (+)
2
RDB
Input
Receive Data B (-)
3
SDA
Output
Send Data A (+)
4
ERA
Output
Data Terminal Ready A (+)
5
SG
-
Signal Ground
6
CSB
Input
Send Possible B (-)
7
SDB
Output
Send Data B (-)
8
CSA
Input
Send Possible A (+)
9
ERB
Output
Data Terminal Ready B (-)
Shell
FG
-
Frame Ground (Common with SG)
9
6
5
1
9
6
5
1
Содержание AGP-3300 Series
Страница 1: ...User Manual AGP 3300 Series ...
Страница 11: ...10 Memo ...
Страница 41: ...AGP 3300 Series User Manual 2 18 Memo ...
Страница 58: ...Chapter 3 Installation and Wiring 3 17 Release Lower the tab and lift the clamp to release the plug Clamp Tab ...
Страница 59: ...AGP 3300 Series User Manual 3 18 Memo ...
Страница 60: ...4 1 4 Settings 1 Types of Settings ...
Страница 74: ...AGP 3300 Series User Manual 4 15 Memo ...
Страница 75: ...AGP 3300 Series User Manual 4 16 ...