AGP-3300 Series User Manual
2-2
2.1
General Specifications
2.1.1
Electrical
2.1.2
Environmental
*1
Extended use in environments where ambient operating temperature is 40°C or higher may degrade the
display quality and result in decreased contrast.
AGP-3300/3301
Series
AGP-3302 Series
Power
Supply
Input Voltage
DC 24V
Rated Voltage
DC19.2V to DC28.8V
Allowable Voltage Drop
5ms (max.)
10ms (max.)
Allowable Ripple Ratio
5% (max.)
Power Consumption
26W (max.)
18W (max.)
In-Rush Current
30A (max.)
Voltage Endurance
AC500V 20mA for 1 minute
Insulation Resistance
DC500V 100M
Ω
(min.)
Physical
Ambient Operating
Temperature
0°C to +50°C
*1
Storage Temperature
-20°C to +60°C
Ambient Humidity
10%RH to 90%RH
(Wet bulb temperature: 39°C max. - no conden-
sation.)
Dust
0.1mg/m
3
max. (non-conductive levels)
Atmosphere
Free of corrosive gasses
Atmospheric
Endurance (AGP
Operation Altitude)
800hPa to 1,114hPa
(2000m max.)
Mechani-
cal
Vibration Resistance
IEC61131-2 compliant
When vibration is NOT continuous
10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s
2
When vibration is continuous
10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s
2
X, Y, Z directions for 10 times (80min.)
Impact Resistance
IEC 61131-2 compliant
(147m/s
2
, X,Y,Z directions for 3 times)
Electrical
Noise Immunity
(via noise simulator)
Noise Voltage: 1,200Vp-p
Pulse Duration: 1µs
Rise Time: 1ns
Electrostatic Dis-
charge Immunity
6kV (complies with EN 61000-4-2 Level 3)
Содержание AGP-3300 Series
Страница 1: ...User Manual AGP 3300 Series ...
Страница 11: ...10 Memo ...
Страница 41: ...AGP 3300 Series User Manual 2 18 Memo ...
Страница 58: ...Chapter 3 Installation and Wiring 3 17 Release Lower the tab and lift the clamp to release the plug Clamp Tab ...
Страница 59: ...AGP 3300 Series User Manual 3 18 Memo ...
Страница 60: ...4 1 4 Settings 1 Types of Settings ...
Страница 74: ...AGP 3300 Series User Manual 4 15 Memo ...
Страница 75: ...AGP 3300 Series User Manual 4 16 ...