InsTallaTIon
EmpyrE ElItE Xt InstallatIOn and OpEratIOn manual
11
trench for underground pipes
1. The water lines
must be properly
insulated to mini-
mize heat loss.
Ask your dealer
for the right un-
derground water
line insulation.
2.
Dig a trench,
minimum 24
in (61 cm)
deep* and 12
in (30 cm) wide, and make as level as
possible to avoid damage to the tubing.
* Trench should be at least 36 inches (91 cm) deep
under driveways.
3. The water lines should be a minimum of 1” (2.54
cm) inside dimensions*, rated and approved for use
with high temperature water.
* Size of water lines depends on distance; consult
with a qualified heating professional to determine
the line size necessary to meet the demands of your
specific application.
4. Identify each water line clearly in order to correctly
locate the supply and return lines.
5. Lay down 14-2 underground wire approved for
underground installation. Obtain the required
electrical permit and confirm local electrical code
requirements prior to installation.
Foundation dimensions
The specifications below provide a stable concrete pad
for the Empyre Elite XT furnace. The open area indicated
by ‘E’ in the drawing provides a channel for plumbing
and electrical conduit.
nOtE:
Furnace can also be installed on concrete patio
blocks.
Empyre Elite XT 100
Empyre Elite XT 200
in
cm
in
cm
A
4
10
5
13
B
40
102
44
112
C
59
150
67
170
D
5
13
5
13
E
10
25
10
25
F
16
41
16
41
House
Shop
Insulated Lines
Typical Installation
Water Lines
Содержание Empyre Elite XT
Страница 1: ...Installation and Operation Instructions Empyre Elite XT Model 100 and 200...
Страница 2: ......
Страница 31: ......