Assembling and connection
2.6. Electrical connection
The electrical connection of the control is only allowed to do by an authorized electronic specialist!
Inform yourself about the connected load of the control and the components before assembling. For the electrical connection
of the control and all of its components apply the current statutory provisions and operational stipulations (e.g. VDE 0100,
EN 60204-1/VDE 0113 part 1)
ATTENTION
Before connecting the control and during repair works on electric components of the
system switch the main switch of the control always on „0“ (OFF)!
Even when the main switch is switched off, the bushing clamps and the main switch are
energized!
Info
We assume no liability for damages resulting from wrong, unprofessional or non approved
electrical connections on the machine! To certifi cate a professional installation of the electric
system, the executing electrician has to provide an acceptance report / inspection sheet.
You can fi nd an electrical connection plan for the control enclosed to this BA and in the
packing of the control.
Important information about the power supply of the control:
- The power supply for the entire control has to be lead over a shared main switch.
- It is
not
allowed to connect the feed line of the EXP300 directly to the ESC300. Connect the feed line of the EXP300
with the main switch, or use a conduit box.
- The charge will be connected self dependent from the control ESC300 (230 V/1~).
- Lines witch a cross section of max. 2,5 mm² can be connected (see scale
page 14
)
The following connected voltages are necessary for a failure-free operation:
- ESC300 (with c relay) -
400 V / 3~/ PE / 50 Hz
(no neutral wire)
- EXP300 (with relay) -
400 V / 3~/ PE / 50 Hz
(no neutral wire)
- Charge -
230 V / 1~ / PE-N
Mount the emergency stop button:
Mount per walkway minimum one emergency stop button. By using several emergency stop buttons and an effective
positioning you are able to increase the safety of your dung removal system.
Mount the emergency stop buttons...
- on a accessible position, and also reachable for smaller persons (e.g. children)
- round danger areas (e.g. wall openings, gates, passages, dropping, drive winch)
- inaccessible for animals
ATTENTION!
If there is not minimum one emergency stop button connected on each alley, it is not al-
lowed to start the operation of the dung removal system!