PrimexEVENT Bell Controller Specifications
PrimexEVENT Bell Controllers, part of the cloud-based OneVue Bell Scheduling system, uses the power of your existing public address
(PA) or school bell system to trigger your school bells.
Ratings
3 VDC Relay operation
Normally Closed (NC) & Normally Open (NO) contacts are rated at: Resistive load: 8A at 250VAC / 30 VDC | Inductive Load: 3.5A at
250VAC / 30 VDC
Power
AC-Power: 5V DC USB Mini B (5 pin) connector interface, 5 ft (1.5 m) cable | Input: 100-240 VAC, 50/60 Hz, 0.4A | Output: 5V DC, 1.0A max.
Optional power extension cable: USB power cable 6.5 feet (2 m), Mini B (5 pin) M and Mini B (5 pin) F connector
Power over Ethernet (PoE): Compliant with IEEE 802.3af standard and compatible with 802.3at standard
Backup Battery Life: estimated up to a maximum of 24 hours of battery life with use of two AA Lithium 1.5V batteries. Use of Energizer®
L91 Ultimate Lithium batteries recommended.
Operation
Alerts: visual LED and LCD display indicators
Stored Schedule Capacity: stores a 7-day schedule in its local memory for each of the two relays. Each night after midnight, the 7-day
schedules are downloaded to the device.
Check-In Interval: hourly; downloads schedules, transmits operating status and event history to OneVue, and synchronizes its time with
NTP time source
Relays: two individual relays; each relay can be wired for NO (Normally Open) or NC (Normally Closed) operation
Dry Contact Inputs: two individual inputs to activate a non-scheduled event (impromptu bell); connected to an external dry contact
closure switch or button
On-board clock: synchronizes its time with an NTP time source to ensure bell schedule accuracy; even after power outages and Daylight
Saving Time shifts
Network Communication
Wireless (Wi-Fi) Networking Protocols
- 802.11b, 11g, 11n single stream (2.4 GHz)
Security Protocols
- None, WEP (Open & Shared), WPA (TKIP & AES), WPA2 (TKIP & AES)
Encryption Protocols
- TLS 1.2
Network Communication Protocols
- Hypertext Transfer Protocol Secure (HTTPS)
IP Addressing
- Dynamic Host Configuration Protocol (DHCP), static IP addressing
Data Packet Size
- typically less than 5 kilobytes (kB)
Enclosure
Enclosure: ABS plastic
Dimension: 4.7" H x 3.7" W x 1.3" D (11.93cm x 9.39cm x 3.30cm)
6
PrimexEVENT Series - Bell Controller Installation Guide
Содержание PrimexEVENT Series
Страница 5: ...Features Specifications Bell Controller...