Connect Bell Controller Relays to Public Address (PA) or Bell System
The Bell Controller device has two independent relays that can be connected to your existing PA or school bell system. Each of the relays
have a separate Normally Open (NO) and Normally Closed (NC) input.
How to connect bell controller relays to PA or bell system
Be sure to follow the installation requirements and installation location guidelines.
The removable terminal connector is provided for simple wiring. The wiring procedure is as follows:
1.
All power to the device and PA or bell system equipment must be turned off.
2.
Remove the terminal connector from the device and make the wiring connections to the terminals.
P3: Relay 1 Normally Closed Contact Input
P4: Relay 1 Common Contact Input
P5: Relay 1 Normally Open Contact Input
P6: Relay 2 Normally Closed Contact Input
P7: Relay 2 Common Contact Input
P8: Relay 2 Normally Open Contact Input
Terminals accept wire gauge from 16-26 AWG.
3.
Reconnect terminal connector to device.
4.
Apply power to device.
WARNING:
Make sure the wires are properly attached to the terminals and the terminal connections are tight. Wires are to be stripped
and there are no loose strands that can cause a short.