AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
23
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
BACnet
BACnet Menu
BACnet Addressing Setup
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied.
MAC set in:
HArdWAre
MAC address
· Hardware – uses DIP switch on BACnet module for
MAC address – default - recommended.
· Software – uses STAT to set MAC address – this OVERRIDES the
hardware switches and could be confusing if you’re not careful.
· Note:
the MAC address (range 1-99) is added to the device instance.
· Example: MAC address = 1, Device instance = 100 – total
address for this Advantage would be 101.
MAC Address
HArdWAre: 1
MAC address
· Display current MAC address.
· Note: DIP switches and software MAC address are only read on startup!
See Device Instance below and Addressing on page 29-30.
deviCe inst.
101
device instance
· This is the ‘software’ BACnet address & MUST be unique on your building site.
· Range: 1 – 4,194,303.
· Note: After changing device instance the STAT will send a RESET command
to the Advantage to apply the ADDRESS changes. Addresses are only
READ on startup, so after any changes you must reset the controller
either via STAT (which is automatic) or cycle 24 VACpower.
· Note: Addresses are only read on startup to prevent a controller with
faulty damaged/improperly set DIP switches from popping up all over
a network, which would be extremely difficult to troubleshoot.
· See MAC address above and Addressing on page 29-30.
BAud rAte
76800
Baud rate
· This sets the BACnet MS/TP baud rate.
· 9600 baud (all BACnet devices must at least support at least this speed) - slowest.
· 19200 baud.
· 38400 baud.
· 76800 baud (default baud rate) - fastest.
Press Menu
tO eXit