AdvAntAge - digitAl vAv diffusers
PRODUCT OVERVIEW & INSTALLATION INSTRUCTIONS
13
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
BACnet netWOrK OPtiOn
Native BACnet is available on each master Advantage diffuser. See page 26 for more details
INSTALLATION
Align the pressure ports on the DMS collar to the control panel
side of the diffuser. Align the flex elbow such that the duct
enters from the control panel side of the diffuser. See DMS
Manual for details.
CAUTION
For accurate flow measurement, the DMS must be installed
with correct alignment between diffuser, DMS collar, and flex
elbow.
DIFFUSER AIR FLOW MEASUREMENT OPTION
The DMS air flow measurement sensor may be added to the Advantage to measure the air flow out of the diffuser. The DPS collar
with SP300 multipoint sensor aligned with the flex elbow provides accurate measurment of air flow throughout the VAV diffuser
operating range. In conjuction with the BACnet Interface option, the measured air flow from each diffuser is available to the
BACnet network using object AV41.
BACnet RJ45 connectors
BACnet screw terminals
Terminal resistor dip switch
MAC address
dip switches