PRODUCT OVERVIEW & INSTALLATION INSTRUCTIONS

4

ACUTHERM ADVANTAGE - Manual 

  |   

acutherm.com

Thermostat Options

The Advantage Master uses a wall 
thermostat to accurately sense room 
temperature in both cooling and heating 
modes.  Each thermostat comes 
complete with a 35ft plenum rated cable 
for connection to the Advantage Master. 

The thermostat is available in six 
options:
•  Room Sensor (Blank Face).
•  Dial Thermostat
•  LCD Thermostat
•  LCD Thermostat with motion sensor 

for occupancy

•  LCD Thermostat with CO2 and 

humidity sensors

•  Wireless Thermostat

The LCD thermostats are used to adjust 
set points, display room temperature, 
and configure the different parameters of 
the diffuser.

nOte   

 When using the Room Sensor 

or Dial Thermostat order a LCD-
SET (minimum of one per project) to 
configure the diffuser.

Thermostat Adjustment

VAV Cooling, VAV Heating - Connecting 

a wall mounted T’stat activates the 

Advantage. Connect the T’stat to 

Advantage using a supplied NETC35 

(35’ plenum rated cable) by snapping 

one side of the plug into jack inside of 

thermostat, and the other side into the 

T’Stat In jack. Setpoint is adjusted using 

the wall mounted sensor.
See page 10 and 11 for more 

thermostat details.

ROOM SENSOR

DIAL THERMOSTAT LCD THERMOSTAT

LCD THERMOSTAT WITH 

CO2 AND HUMIDITY

LCD THERMOSTAT 

WITH MOTION

SENSOR

WIRELESS 

THERMOSTAT

figure 8 - drOne Wiring diAgrAM   

RED LED

DC SIGNAL STATUS TO DRONE

GREEN LED

24 VAC SIGNAL STATUS

1 & 6 = 2 -10VDC

2 & 5 = COMMON

3 & 4 = 24VAC

FROM PREVIOUS

DIFFUSER

CABLE

CABLE

TO NEXT

DIFFUSER

INTERNAL WIRING

Содержание Acutherm Advantage Master

Страница 1: ...v200 Issue Date 12 30 21 2021 Acutherm All rights reserved MANUAL INSTALLATION Advantage Advantage Digital VAV Diffusers...

Страница 2: ...nformation Menu LCD Stats only 14 Service Menu LCD Stats only 15 Balancing Menu 16 VVT Menu Pressure Dependant Mode 17 Setpoint Menu Setpoint Limits and Temperature Units 18 Input Menu Supply Air Temp...

Страница 3: ...ing Notify carrier if external damage exists Submit all claims for shipping damage to the carrier 2 Move diffusers in cartons to installation area Note any unit identification 3 Remove cardboard box a...

Страница 4: ...unding Secondary power supply will be factory connected to pluggable 24 VAC PWR terminal block See Mounting Installation instructions on Page 9 if transformer is shipped separately 3 Advantage Power M...

Страница 5: ...xtended by using a CC cable connector for longer runs A maximum of five ADVD can be supported by one Advantage Master ADVM Each ADVD draws 3 0 VA APM PPM 115 277 POWER SUPPLY ONE OUTPUT JACK MASTER CS...

Страница 6: ...parameters of the diffuser NOTE When using the Room Sensor or Dial Thermostat order a LCD SET minimum of one per project to configure the diffuser Thermostat Adjustment VAV Cooling VAV Heating Connec...

Страница 7: ...override open command using the menus availble on the LCD thermsotat Service Menu Balanacing Dpr Override Goto Full Open see Balancing Menu page 16 or if the Advantage is on a BACnet network setting...

Страница 8: ...not specified Pulse Delay Modulation Reheat relay is on for a minimum of 2 minutes when required OFF Cycle is proportional to heating requirement Suitable for hydronic systems where entire system is...

Страница 9: ...longer runs Fig 6 page 3 210ft maximum CSJ Cable Splitters used to daisy chain power between masters Fig 6 page 3 Power switch with indicator LED Installation Instructions 1 Turn off power switch Rem...

Страница 10: ...r the PLD Advantage Linear Diffuser The Advantage Pressure Relief Collar PRC slips over the Advantage inlet to provide a simple and inexpensive method to control duct static pressure The PRC s dual sh...

Страница 11: ...ensing All master units have a temperature sensor located near the inlet for automatic heating cooling changeover For automatic changeover the Advantage uses a dynamic neutral mode for optimal use of...

Страница 12: ...ermostat is powered from the controller Measures room temperature Set point can be adjusted from a hidden dial on the back of the T Stat using a small flat head screw driver Set point limits can be ad...

Страница 13: ...k The LCD Thermostat with Motion Sensor can be used as a balancing tool for the Intelligent Controller system by simply connecting the RJ 45 cable to the back of the thermostat This thermostat can als...

Страница 14: ...rtion of the thermostat first and then snapping the bottom half in 3 All thermostats will come equipped with a 0 050 Allen key for the set screw at the bottom 1 25 32 Wall Fasteners by others Surface...

Страница 15: ...urate flow measurement the DMS must be installed with correct alignment between diffuser DMS collar and flex elbow DIFFUSER AIR FLOW MEASUREMENT OPTION The DMS air flow measurement sensor may be added...

Страница 16: ...crease push buttons for day set point adjustment DAY SETPOINT 75 0 F DAY SETPOINT SAVING CONTROLLER LCD THERMOSTAT STANDARD MODEL Displays firmware version of thermostat LCD THERMOSTAT VERSION X XX LO...

Страница 17: ...isplay air flow rate DAMPER POS 50 Damper Position This indicates the current position of the damper in percent Range is 0 100 100 full open or maximum air DAMPER TARGET 50 Target damper target in VVT...

Страница 18: ...tpoint Setup of Setpoint limits day minimum maximum F C selection See page 18 INPUT Input Shows supply air temperature reading Shows if VAV and BACnet modules are attached See page 19 OUTPUT Output Al...

Страница 19: ...damper full close PRESS MENU TO EXIT Exit This will exit the info menu if you select Yes Note Info menu will automatically time out after 60 seconds Balancing Menu Scroll through with Up and Down butt...

Страница 20: ...Unocc Dpr Pos When Advantage is unoccupied damper will rest at this position Range 0 100 Default 0 INLET SIZE 10 INCHES Inlet Size Size of the diffuser inlet factory set K FACTOR 1500 K Factor If no D...

Страница 21: ...is heating setpoint when unoccupied Range 10 0 F 100 0 F Default 62 0 F NITE COOL SET 83 0 F Night Cool Setpoint Advantage will maintain this cooling setpoint when unoccupied Range 10 0 F 100 0 F Defa...

Страница 22: ...ure to enable heating Cold Switch set SAT temperature to enable cooling Neutral Mode Force Cool Locks the diffuser in the cooling mode Neutral Mode Force Heat Locks the diffuser in the heating mode RM...

Страница 23: ...hts When using Motion T Stat output controls room lights USED AS FORCE OFF Force Off Output de energized at all times USED AS FORCE ON Force On Output energized at all times REHEAT TYPE ON OFF Reheat...

Страница 24: ...tputs this voltage on Auxiliary Analog pin when there is a maximum call for cooling Default 10 0 VDC AUX HEAT MIN 0 0 VDC Auxiliary Heat min Voltage Outputs this voltage on Auxiliary Analog pin when t...

Страница 25: ...ddress are only read on startup See Device Instance below and Addressing on page 29 30 DEVICE INST 101 Device Instance This is the software BACnet address MUST be unique on your building site Range 1...

Страница 26: ...low or Skys SOUND OPTIONS LIMITS ONLY Thermostat Sound Limits Only stat will beep when user tries to exceed a limit default All off beeper disabled All on stat will beep when user exceed a limit or st...

Страница 27: ...application model Square Round Swirl or Linear PRESS MENU TO EXIT CO2 Settings Menu Menu item will only appear if thermostat with CO2 sensor connected See thermostat with CO2 for more details Advanta...

Страница 28: ...r is a 35 foot plenum rated network cable to simplify installation in the field Local addresses can be set at each Advantage diffuser using the on board DIP switches The media access control MAC addre...

Страница 29: ...The terminating can be done with a 100 ohm resistor across the and lines Advantage Diffusers have the option for enabling termination via a DIP switch or by a software menu selection Turning on termi...

Страница 30: ...twisted pairs one for and one for NET COM Twisted pair and reference or 3 conductor Low capacitance 17pF or less Plenum rated FT6 CMP ratings 100 120 ohm Balanced CAT5 CAT5E CAT6 network cable has ex...

Страница 31: ...Service Menu Hold down the Menu button on the LCD Thermostat for 5 seconds until prompted for a passcode use and to enter the passcode DOWN UP UP DOWN The screen will now display Service Menu Applicat...

Страница 32: ...the same speed Acutherm controllers are defaulted to a baud rate of 76800 but can be changed to 38400 19200 or 9600 For a network segment with all Acutherm controllers including Acutherm PRTU systems...

Страница 33: ...is obtained NOTE Each device on a network segment must be set to run at the same speed or baud rate Description Default Value Factory Notes Mac Address 6 Value limited to 1 99 Tier 1 x100 58 Value lim...

Страница 34: ...ne Signals Supply Air Temperature Test Procedure Advantage Response Response Time Varies allow at least 5 minutes COLD Supply Air Temperature 2 F 1 C cooler than Room Temperature Adjust setpoint for m...

Страница 35: ...some power cables to another jack Faulty Cable or Connector First Disconnect all cables and connectors originating from problem outlet Next Reconnect first C35 cable only If Red fault LED lights cabl...

Страница 36: ...ports 9600 19200 38400 76800 baud rates 2x RJ45 connections Green Transmit LED Red Receive LED MAC address settable through DIP switches or LCD thermostat Device Instance settable through LCD thermost...

Страница 37: ...Advantage Digital VAV Diffusers PRODUCT OVERVIEW INSTALLATION INSTRUCTIONS 35 acutherm com ACUTHERM ADVANTAGE Manual NOTES...

Страница 38: ...ve Suite 280 Dublin CA 94568 USA Tel 1 510 785 0510 Send your questions to info acutherm com This document contains the most current product information as of this printing For the most up to date pro...

Отзывы: