AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
19
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
setPOint
set lO liMit*
65.0°f
day setpoint low limit
· This is the lowest Setpoint allowed
· Range: 10.0°F – 100.0°F Default: 65.0°F
set Hi liMit*
80.0°f
day setpoint High limit
· This is the lowest Setpoint allowed
· Range: 10.0°F – 100.0°F Default: 80.0°F
teMP. units
fAHrenHeit
temperature units
· Fahrenheit or Celsius
· Default: °F
nite HeAt set*
62.0°f
night Heat setpoint
· Advantage will maintain this heating setpoint when unoccupied
· Range: 10.0°F – 100.0°F Default: 62.0°F
nite COOl set*
83.0°f
night Cool setpoint
· Advantage will maintain this cooling setpoint when unoccupied
· Range: 10.0°F – 100.0°F Default: 83.0°F
PrO. BAnd*
2.0°f
Proportional Band
· Set the proportional band of the PI controller
· Default: 2.0°F
dAY diff.*
1.0°f
day differential
· Set the day differential (also known as dead band)
· Default: 1.0°F
Press Menu
tO eXit
exit
setpoint Menu
Setpoint Limits and Temperature Units
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied.
*
Also available over BACnet network if diffuser has BACnet option installed.