AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
22
ACUTHERM ADVANTAGE - Manual
|
acutherm.com
Output Analog Menu
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied.
OutPut
OutPut
AuX BinArY
See
Output Aux Binary Menu (previous page)
OutPut
AnAlOgs
AuX. COOl Min
0.0 vdC
Auxiliary Cool Min voltage
· Outputs this voltage on Auxiliary Analog pin when there is a minimum call for cooling.
· Default: 0.0 VDC.
AuX. COOl MAX
10.0 vdC
Auxiliary Cool Max voltage
· Outputs this voltage on Auxiliary Analog pin when there is a maximum call for cooling.
· Default: 10.0 VDC.
AuX. HeAt Min
0.0 vdC
Auxiliary Heat min voltage
· Outputs this voltage on Auxiliary Analog pin when there is a minimum call for heating.
· Default: 0.0 VDC.
AuX HeAt MAX
10.0 vdC
Auxiliary Heat Max voltage
· Outputs this voltage on Auxiliary Analog pin when there is a maximum call for heating.
· Default: 10.0 VDC.
AuX deAdBAnd
0.0 vdC
Auxiliary idle voltage
· Outputs this voltage on Auxiliary Analog pin when there is no call for heating or cooling
(deadband).
· Default: 0.0 VDC.
AuX. unOCC.
0.0 vdC
Auxiliary unoccupied voltage
· Outputs this voltage when Auxiliary Analog pin is set to unoccupied.
Press Menu
tO eXit
Press Menu
tO eXit