Large Display Temperature Meters
Instruction Manual
37
Programming Alarm Points Using Set Points (
setpts
)
Menu
Note
To simplify programming, write down the desired programming values
prior to attempting to program the meter. The
Programmed
Parameter Settings
form, located on page 69, provides a convenient
method to record the user settings; it also provides the factory setting
for most of the programmable parameters.
Press
ENTER,
then press
ENTER
again when set
points (
SEtPtS
) function appears. The display will
scroll through the set points. Press
ENTER
when
the desired set point is displayed to program that
set point.
SEtPtS
To program set points values
The display scrolls through
set 1
,
Set 2
,
set 3, set 4
,
for alarm set point 1 through alarm set point 4. Press
ENTER
when desired set point appears.
After
Set 4
is displayed or programmed, the meter will exit
the
SetptS
(set points) menu and move to the next
programming menu.
output
will be displayed, if 4-20 mA transmitter output
option is installed.
SEt 1
then
SEt 2
then
SEt 3
then
SEt 4
then
outPut
If
ENTER
is pressed while a set point is shown,
the display will then show a flashing number.
Program the desired set point value per
Five Basic Digit/Display-Setting
Instructions
on
page 31.
SEt 1
then
00100F
Alarm Set and Reset Programming Confirmation
To verify that the alarm set and reset points have been programmed as desired,
press
ENTER
, and press
ENTER
again when
sEtPtS
appears, the display will
scroll through set points 1 through 4. Press
ENTER
when the desired set point is
shown. Before the display stops flashing set point value, press enter to advance
the display to reset point.